Figure 12-32. RS-485 DB-37 to BE1-CDS240

IRIG Input and Connections

The IRIG input is fully isolated and supports IRIG Standard 200-98, Format B002. The demodulated (dc

level-shifted) input signal must be 3.5 volts or higher to be recognized as a high logic level. The maximum

acceptable input voltage range is +10 volts or –10 volts (a 20 volt range). Input burden is nonlinear and

rated at approximately 4 kΩ at 3.5 Vdc and approximately 3 kΩ at 20 Vdc.
IRIG connections are located on a terminal block shared with the RS-485 and input power terminals.

Terminal designations and functions are shown in Table 12-4.

Table 12-4. IRIG Terminal Assignments

Terminal

Function

A1

(+) Signal

A2

(-) Reference


9365200990 Rev M

BE1-CDS240 Installation

12-27