Irig input and connections, Irig input and connections -27, Figure 12-32. rs-485 db-37 to be1-cds240 -27 – Basler Electric BE1-CDS240 Installation User Manual
Page 29: Table 12-4. irig terminal assignments -27
Figure 12-32. RS-485 DB-37 to BE1-CDS240
IRIG Input and Connections
The IRIG input is fully isolated and supports IRIG Standard 200-98, Format B002. The demodulated (dc
level-shifted) input signal must be 3.5 volts or higher to be recognized as a high logic level. The maximum
acceptable input voltage range is +10 volts or –10 volts (a 20 volt range). Input burden is nonlinear and
rated at approximately 4 kΩ at 3.5 Vdc and approximately 3 kΩ at 20 Vdc.
IRIG connections are located on a terminal block shared with the RS-485 and input power terminals.
Terminal designations and functions are shown in Table 12-4.
Table 12-4. IRIG Terminal Assignments
Terminal
Function
A1
(+) Signal
A2
(-) Reference
9365200990 Rev M
BE1-CDS240 Installation