background image

Settings

Settings for your application should be entered and confirmed before placing the relay in service. Register

settings such as breaker operations and breaker duty can be entered to match the current state of your

system.

Preparing the Relay for Service

Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or

solid-state component relays. Both must be wired together with inputs, outputs, and have operating

settings applied. Logic settings determine which protection elements are electronically wired to the inputs

and outputs of the device. Operating settings determine the pickup thresholds and time delays. The logic

and operating settings should be tested by applying actual inputs and operating quantities and verifying

proper output response. For more details, refer to Section 13, Testing and Maintenance. All of the

following connections and functions should be verified during commissioning tests:

• Proper connection and sensing of current and voltage signals

• Input and output contact connections

• I/O sensing versus virtual sensing

• Settings validation

• Proper operation of equipment (main or auxiliary)

• Proper alarming (to SCADA) and/or targeting

Refer to Section 7, BESTlogic Programmable Logic, for information about customizing preprogrammed

logic and creating user-defined logic and Section 8, Application, for information about the application of

preprogrammed logic schemes.

Communications Connections

The following paragraphs describe the communication connections for the BE1-CDS240. Section 11,

ASCII Command Interface, provides information about using the relay communication interface and lists

all communication commands along with a description and the syntax for each command.

RS-232 Connectors

Front and rear panel RS-232 connectors are Data Communication Equipment (DCE) DB-9 female

connectors. Connector pin numbers, functions, names, and signal directions are shown in Table 12-2 and

Figure 12-27. RS-232 cable connection diagrams are provided in Figures 12-28 through 12-31. Optional

Clear to Send (CTS) and Request to Send (RTS) connections are required only if hardware handshaking

is enabled.

Table 12-2. RS-232 Pinouts (COM0 and COM1)

Name

Function

Name

Direction

1

Shield

----

N/A

2

Transmit Data

(TXD)

From relay

3

Receive Data

(RXD)

Into relay

4

N/C

----

N/A

5

Signal Ground

(GND)

N/A

6

N/C

----

N/A

7

N/C

----

N/A

8

N/C

----

N/A

9

N/C

----

N/A




12-24

BE1-CDS240 Installation

9365200990 Rev M