1-4

BE1-47N General Information

9170400990 Rev J

Time Delay

Definite

Setting Range ...................... 0.1 to 9.9 s

Increment ............................. 0.1 s

Accuracy .............................. ±5% or ±50 ms of the time setting

Inverse

Setting Range ...................... 01 to 99

Increment ............................. 1

Accuracy .............................. ±5% or ±50 ms of the indicated time of the selected time-dial curve

illustrated in Figure 3-3

Instantaneous

Delay .................................... <50 ms

Undervoltage

Pickup

Setting Range ............................ 2 to 32% below nominal

Increment ................................... 2%

Accuracy..................................... ±1% of the pickup setting

Dropout ............................................. 98% of pickup
Time Delay

Definite

Setting Range ...................... 0.1 to 9.9 s

Increment ............................. 0.1 s

Accuracy .............................. ±5% of the time setting

Inverse

Setting Range ...................... 01 to 99

Increment ............................. 1

Accuracy .............................. ±5% or ±50 ms of the indicated time of the selected time-dial curve

illustrated in Figure 3-3

Instantaneous

Delay .................................... <50 ms

Overvoltage

Pickup

Setting Range ............................ 2 to 32% above nominal

Increment ................................... 2%

Accuracy..................................... ±1% of the pickup setting

Dropout ............................................. 98% of pickup
Time Delay

Definite

Setting Range ...................... 0.1 to 9.9 s

Increment ............................. 0.1 s

Accuracy .............................. ±5% of the time setting

Inverse

Setting Range ...................... 01 to 99

Increment ............................. 1

Accuracy .............................. ±5% or ±50 ms of the indicated time of the selected time-dial curve

illustrated in Figure 3-3

Instantaneous

Delay .................................... <50 ms