Outputs, Main outputs, Output option – Basler Electric BE1-47N User Manual

Page 22: Auxiliary outputs, Style chart option 3

Advertising
background image

3-6

BE1-47N Functional Description

9170400990 Rev J

Outputs

BE1-47N outputs consist of the main, tripping output relays, auxiliary output relays, and a power supply

status output relay.

Main Outputs

Output relays, rated for tripping duty, are provided for each protection function. Normally open (NO) or

normally closed (NC) relay contacts may be specified for each protection function. Table 3-3 lists the

possible output relay configurations.

Table 3-3. Main Output Contact Configurations

Output

Option

Protection

Function

Output

Configuration

NO

NC

E

47N

F

47N

27/59

G

47N

H

47N

27/59

N

47N

27/59

P

47N

27/59

Auxiliary Outputs

Auxiliary output relays that operate at the same time as the main output relays are also available (style

chart option 3). Table 3-4 lists the possible auxiliary output relay configurations.

Table 3-4. Auxiliary Output Contact Configurations

Style Chart

Option 3

Protection

Function

Output

Configuration

NO

NC

0

N/A

1

47N

2

47N

3

47N

27/59

4

47N

27/59

7

47N

27/59

8

47N

27/59


Advertising