Power supply status output, Indicators, Power supply – Basler Electric BE1-47N User Manual

Page 23: Target indicators, Internally operated targets, Current operated targets

Advertising
background image

9170400990 Rev J

BE1-47N Functional Description

3-7

Power Supply Status Output

The power supply status relay has a set of normally closed contacts and energizes when operating power

is applied to the BE1-47N. If relay operating power is lost or either side of the power supply output (+12

Vdc or –12 Vdc) fails, the power supply status relay de-energizes and opens the power supply status

output contacts.

Indicators

LEDs indicate power supply status and protection function pickup.
The power LED lights when operating power is applied to the relay and the relay power supply is

operating normally.
One LED is provided for each protection function. An LED lights when the function’s setpoint is exceeded

and the protection function is timing toward a trip.

Power Supply

Operating power for the relay circuitry is supplied by a wide range, electrically isolated, low-burden power

supply. Power supply operating power is not polarity sensitive. The front panel power LED and power

supply status output indicate when the power supply is operating. Power supply specifications are listed in

Table 1-1.

Target Indicators

Target indicators are optional components selected when a relay is ordered. The electronically latched

and reset targets consist of red LED indicators located on the relay front panel. A latched target is reset

by operating the target reset switch on the front panel. If relay operating power is lost, any illuminated

(latched) targets are extinguished. When relay operating power is restored, the previously latched targets

are restored to their latched state.
A relay can be equipped with either internally operated targets or current operated targets.

The relay trip outputs are directly applied to drive the appropriate target indicator. Each indicator is

illuminated regardless of the current level in the trip circuit.

Internally Operated Targets

A current operated target is triggered by closure of the corresponding output contact

Current Operated Targets

and

the presence of

at least 200 milliamperes of current flowing in the trip circuit.

NOTE

Prior to September 2007, BE1-47N target indicators consisted of magnetically

latched, disc indicators. These mechanically latched target indicators have

been replaced by the electronically latched LED targets in use today.