BE1-47N Functional Description

3-1

SECTION 3 • FUNCTIONAL DESCRIPTION

Introduction

BE1-47N relay functions are illustrated in Figure 3-1 and described in the following paragraphs.

Figure 3-1. Function Block Diagram

Voltage Sensing

One of two nominal voltage levels may be specified for a system frequency of 50 hertz or 60 hertz.

Voltage sensing input options are summarized in Table 3-1.

Table 3-1. Voltage Sensing Input Options

Sensing Input Option

Nominal Voltage

Frequency

3

120 Vac

60 Hz

4

100 Vac

50 Hz

5

208 Vac

60 Hz

6

173 Vac

50 Hz


Three-phase system voltage is supplied to internal potential transformers (PTs). These PTs are an

integral part of the sequence filter and provide isolation, step-down scaling, and phasor summation to

eliminate the zero-sequence component of the sensed voltages.

V

C

TARGET

47N

POWER SUPPLY

STATUS

D2818-12

07-30-98

V

B

V

A

PHASE

SHIFT

PICKUP

SCALING

LOW

PASS

FILTER

REFERENCE

LEVEL

NEGATIVE

SEQUENCE

VOLTAGE

COMPARATOR

AND

47N

AUX.

TIMING

TARGET

27/59

AUX.

OR

TIMING

TIMING

POWER

SUPPLY

SENSOR

59

27

UNDERVOLTAGE

COMPARATOR

UNDERVOLTAGE

PICKUP

OVERVOLTAGE

PICKUP

OVERVOLTAGE

COMPARATOR

LOW

PASS

FILTER

POWER

SUPPLY

SENSOR

POWER

TO INTERNAL

CIRCUITRY

OPERATING

POWER

V

2

SEQUENCE

FILTER