Verification tests, Definite time verification, Inverse time verification – Basler Electric BE1-47N User Manual

Page 39

Advertising
background image

9170400990 Rev J

BE1-47N Testing

5-3

4. Raise the input voltage until the Undervoltage Pickup LED turns off. Record the input value. Dropout

should be within 2.0% of the pickup value (i.e., input voltage at time of pickup, LED on).

Verification Tests

Verification tests consist of definite time verification and inverse time verification.

Definite Time Verification

The definite time circuitry for the negative sequence voltage (47N), overvoltage (59), and undervoltage

(27) functions operates similarly and can be tested using the same philosophy. In order to reduce the

amount of redundant procedural steps, only the overvoltage function is addressed here.
1. Connect the test setup as indicated in Figure 5-2.
2. Adjust the Overvoltage Time Delay switch to 33.
3. Adjust the Overvoltage Pickup switch to the A (2%) position.
4. Connect the voltage source to case terminals 7 (A-phase) and 8 (C-phase) and adjust the voltage

source to 1.20 times the nominal input value (120%).

5. Close switch S1 to initiate the timer. The Overvoltage Pickup LED will light and the timer should time

out at 3.3 seconds ±5%.

Inverse Time Verification

Due to the similarities in inverse timing for the functions of this relay, only the negative sequence function

is addressed here. The remaining functions can be verified using the same test philosophy.
1. Connect the test setup as indicated in Figure 5-1.
2. Adjust the Negative Sequence Pickup switch to the B (4%) position. Adjust the Negative Sequence

Time Delay switch to 10.

3. Short or jumper case terminals 7 (B-phase) and 8 (C-phase).
4. Using Table 5-2 as a guide, apply voltage at case terminals 6 (A-phase) and 7 (C-phase). Note that

the input voltage values are two times the actual pickup value.

Table 5-2. Inverse Time Test Voltage

Sensing Input Range

Voltage Input

3) 120 Vac, 60 Hz

16.628 Vac +0.17 Vac, 60 Hz

4) 100 Vac, 50 Hz

13.856 Vac +0.14 Vac, 50 Hz

5) 208 Vac, 60 Hz

28.80 Vac +0.29 Vac, 60 Hz

6) 173 Vac, 50 Hz

24.00 Vac +0.24 Vac, 50 Hz


5. Measure and record the interval from initiate to contact closure at case terminals 1 and 10. The 47N

inverse time should be 5.96 +0.298 seconds.
Further points on the inverse time curves may be verified using the same philosophy. Input voltage

values for pickup may be obtained using the equations mentioned previously.