Resistive ratings, Inductive ratings, Current operated targets – Basler Electric BE1-27 User Manual

Page 13: Output, Contacts, Power, Supply -5, Target, Indicators, Type

Advertising
background image

9170600990 Rev L

BE1-27/59 General Information

1-5

Output Contacts

120 Vac ............................................. Make, break, and carry 7 Aac continuously

Resistive Ratings

250 Vdc ............................................. Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,

break 0.3 Adc

500 Vdc ............................................. Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,

break 0.3 Adc

120 Vac, 125 Vdc, 250 Vdc .............. Break 0.3 A (L/R = 0.04)

Inductive Ratings

Power Supply

Power supply types and specifications are listed in Table 1-1.

Table 1-1. Power Supply Ratings

Type

Nominal

Input Voltage

Input Voltage

Range

Burden at

Nominal

K (midrange)

48 Vdc

24 to 150 Vdc

3.8 W

J (midrange)

125 Vdc

24 to 150 Vdc

4.0 W

120 Vac

90 to 132 Vac

17.1 VA

L (low range)

24 Vdc

12 to 32 Vdc *

3.9 W

Y (midrange)

48 Vdc

24 to 150 Vdc

3.8 W

125 Vdc

24 to 150 Vdc

4.0 W

Z (high range)

250 Vdc

68 to 280 Vdc

4.1 W

240 Vac

90 to 270 Vac

28.4 VA

*

Type L power supply initially requires 14 Vdc to begin operating. Once operating, the input voltage may

be reduced to 12 Vdc and operation will continue.

Target Indicators

Electronically latched, manually reset target indicators are optionally available to indicate closure of the

trip output contacts. Either internally operated or current operated targets may be specified. Internally

operated targets should be selected when normally closed (NC) output contacts are specified.

Minimum Rating ................................ 200 mA flowing through the trip circuit

Current Operated Targets

Continuous Rating ............................ 3 A

1 Second Rating ............................... 30 A

2 Minute Rating................................. 7 A

Type Tests

Shock ................................................ Withstands 15 G in each of three mutually perpendicular planes

without structural damage or performance degradation.

Vibration ............................................ Withstands 2 G in each of three mutually perpendicular planes,

swept over the range of 10 to 500 Hz for a total of six sweeps, 15

minutes each sweep, without structural damage or degradation of

performance.

Dielectric Strength ............................ Tested in accordance with IEC 255-5 and IEEE C37.90: 2,000 Vac

applied for 1 min

Impulse Test ..................................... Qualified to IEC 255-5