BE1-27/59 Testing

5-1

SECTION 5 • TESTING

Introduction

The following procedures verify proper relay operation and calibration.
Results obtained from these procedures may no fall within specified tolerances. When evaluating results,

consider three prominent factors:

Test equipment accuracy

Testing method

External test set components tolerance level

Required Test Equipment

Minimum test equipment required for relay testing and adjustment is listed below. Refer to Figure 5-1 for

the test setup.

NOTE

Commercially available frequency relay test sets with frequency and time

generating accuracies exceeding those of the relay and including electronic

switching, may be used.

Appropriate ac or dc power source for relay operation.

Appropriate ac source for frequency sensing. (A source with frequency stability of 0.00002 Hz

must exhibit phase noise of less than 90 db for accurate measurement. The accuracy and

stability of this source is necessary as the relay precisely measures the period between positive

going zero-crossings of the applied waveform and responds instantaneously to the sensed

condition.)

Hardware (battery and lamp, multimeter, etc.) or method of determining that the output contacts

close.

Operational Test

Power Supply Status Output (Option 2-A or B)

Step 1.

With the unit in a powered-up condition, verify that the power supply status output contacts

are energized open.

Step 2. Remove input power and verify that the status output contacts close.

Pickup

Step 1.

Connect the test circuits shown in Figure 5-1 as necessary for the functions included in your

relay model. See Table 5-1. Turn all undervoltage pickup controls fully CCW and all

overvoltage pickup functions fully CW. Set all time delay controls to 00. Adjust T1 to nominal

voltage for your sensing input range as indicated below.

Table 5-1. Sensing Input Range

Sensing Input Range

2

3

4

120 Vac

120 Vac

240 Vac