N table 2-1 – Basler Electric BE1-27 User Manual

Page 16

Advertising
background image

2-2

BE1-27/59 Controls and Indicators

9170600990 Rev L



Table 2-1. Control and Indicator Descriptions

Locator

Description

A

Undervoltage Pickup Control. Establishes setpoint for the timed undervoltage function.

Continuously adjustable over the range defined by the style number.

B

Undervoltage Time Delay Control. Establishes the interval between undervoltage pickup

and the time delayed output. Defined by the style number, this delay is either a user-

adjustable definite time or inversely proportional to the magnitude of the undervoltage

condition. A setting of 0.0 provides an instantaneous response.
Definite - adjustable from 0.0 to 9.9 seconds in 0.1 second increments.
Inverse

C

- adjusts inverse timing characteristic curve relative to the time axis. (See the

characteristic curves in Section 3.)
Undervoltage Instantaneous Control. Establishes setpoint for the instantaneous

undervoltage function. Continuously adjustable over the range defined by the style

number.

D

Overvoltage Pickup Control. Establishes setpoint for the timed overvoltage function.

Continuously adjustable over the range defined by the style number.

E

Overvoltage Time Delay Control. Establishes the interval between overvoltage pickup

and the time delayed output. Defined by the style number, this delay is either a user-

adjustable definite time or inversely proportional to the magnitude of the overvoltage

condition. A setting of 0.0 provides an instantaneous response.
Definite - adjustable from 0.0 to 9.9 seconds in 0.1 second increments.
Inverse

F

- adjusts inverse timing characteristic curve relative to the time axis. (See the

characteristic curves in Section 3.)
Overvoltage Instantaneous Control. Establishes setpoint for the instantaneous

overvoltage function. Continuously adjustable over the range defined by the style

number.

G

Power Indicator. This red LED lights when operating power is applied to the relay.

H

Target Reset Switch. This switch is operated to reset the target indicators.

I

Overvoltage Pickup LED. A red LED that illuminates when overvoltage exceeds the

pickup setting.

J

Target Indicators. The electronically latched red target indicators illuminate when the

corresponding output relay energizes. To ensure proper operation of current-operated

targets, the current flowing through the trip circuit must be 200 mA or higher. Target

indicators are reset by operating the target reset switch (locator H).

K

Output Test Pushbuttons. These pushbuttons allow manual actuation of the output relays.

Output relay actuation is achieved by inserting a nonconductive rod through the front

panel access holes.

L

Undervoltage Pickup LED. A red LED that illuminates when undervoltage exceeds the

pickup setting.