BE1-27/59 Testing

5-5

Step 4.

Set the time delay control for the function being tested to 01 (0.1 seconds). Press and

release S2 to assure that K1 is de-energized. Reset the timer. Press and release S1.

RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 1 of

Table 5-4.

Step 5.

Press and release S2. Set the time delay control for the function being tested to 99 (9.9

seconds). Reset the timer. Press and release S1.

RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 2 of

Table 5-4.

Step 6.

Repeat Steps 1 through 5, as necessary, for each function’s time delay control.

This concludes the operational test procedure.