BE1-27/59 Functional Description

3-1

SECTION 3 • FUNCTIONAL DESCRIPTION

Introduction

BE1-27, BE1-59, and BE1-27/59 relay functions are illustrated in Figure 3-1 and described in the following

paragraphs.

Figure 3-1. Function Block Diagram

System Voltages

The BE1-27, BE1-59, and BE1-27/59 relays are available with three sensing input ranges. The 55 to

160V range is intended for use with nominal system voltages of 120V or 69V (120 ÷ √3). The 110 to 320V

range is intended for use with nominal system voltages of 240V, 208V (120 x √3) or 277V (480 ÷ √3). The

1 to 40V range is intended for use with a wye/broken delta PT configuration with 120V or 69V (120 ÷ √3)

line-to-ground secondary voltages. The wye/broken delta PT configuration is a zero sequence filter

capable of producing three times the line-to-ground voltage (3Vo).

AUX.

TARGET

AUX.

AUX.

AUX.

POWER

SUPPLY

STATUS

OV TIME

DIAL

OV

TIMER

TIMED

OV

COMPARATOR

OV

PICKUP SETTINGS

INST.

TIMED

UNDER

OVER

UNDER

OVER

UV TIME

DIAL

UV

TIMER

TIMED

UV

COMPARATOR

UV

INST.

OV

COMPARATOR

INST.

UV

COMPARATOR

POWER

SUPPLY

SENSOR

UV

POWER

SUPPLY

SENSOR

TO INTERNAL

CIRCUITRY

FULL-WAVE

RECTIFIER

LOW-PASS

FILTER

MONITORED

VOLTAGE

OPERATING

POWER

D2354-03

03-11-96

TARGET

TARGET

TARGET