5-4

BE1-27/59 Testing

9170600990 Rev L

Step 7.

Slowly increase the T1 voltage until the OVER PICKUP indicator and the timed and

instantaneous overvoltage test indicators illuminate. Measure and record the voltage.

RESULT: This voltage is between 156.8 and 163.2 Vac for Sensing Input Range 3 or between 313.6

and 326.4 for Sensing Input Range 4.

NOTE

Step 8 applies only to BE1-59 relays with Sensing Input Range 3 or 4.


Step 8.

Decrease the T1 voltage to 50 Vac. Turn all overvoltage pickup controls fully CCW. Slowly

increase the T1 voltage until the OVER PICKUP indicator and the timed and instantaneous

overvoltage test indicators illuminate. Measure and record the voltage.

RESULT: The voltage is between 53.9 and 56.1 Vac for Sensing Input Range 3 or between 107.8 and

112.2 Vac for Sensing Input Range 4.

This concludes the pickup test.

Timing

The following procedure verifies timing characteristics.
Step 1.

Connect the test circuit shown in Figure 5-2. Output terminal connections are dependent on

the function to be tested. See Table 5-1.

Step 2.

Adjust the under or overvoltage pickup settings and the T1 and T2 tap voltage levels as

indicated in Table 5-3 below for the function being tested.

Table 5-3. T1 and T2 Tap Voltage Levels

Sensing

Range

Over

Pickup

Under

Pickup

T1

Voltage

T2

Over Under

2

30

20

40

3

120

100

110

152

68

4

240

200

220

304

136


Step 3.

Set the time delay control for the function being tested to 00 (50 ms or less). Press and

release S2 to assure that K1 is de-energized. Reset the timer. Press and release S1.

RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 1 of

Table 5-4.

Table 5-4. Timing Test Results

Timing Type

Column 1

Column 2

Instantaneous

50 ms or less

50 ms or less

Definite

0.050 to 0.150 sec

9.702 to 10.098 sec

Under

Over

Under

Over

Short Inverse

0.087 to 0.187 sec

0.092 to 0.192 sec

6.231 to 6.687 sec

6.557 to 7.247 sec

Medium Inverse

0.292 to 0.392 sec

0.307 to 0.407 sec

24.626 to 27.218 sec

25.991 to 28.727 sec

Long Inverse

0.553 to 0.653 sec

0.583 to 0.683 sec

49.185 to 54.363 sec

51.895 to 57.358 sec