1 • general information, Purpose, Application – Basler Electric BE1-27 User Manual

Page 9: Section 1, General information -1, Motor, Protection, Automatic, Transfer, Switching

Advertising
background image

9170600990 Rev L

BE1-27/59 General Information

1-1

SECTION 1 • GENERAL INFORMATION

Purpose

The BE1-27 Undervoltage, BE1-59 Overvoltage and the BE1-27/59 Under/Overvoltage Relays are solid-

state devices that provide reliable protection for generators, motors, and transformers against adverse

system voltage conditions.

Application

Electric power systems are designed for constant voltage operation. Loads utilizing commercial electric

power are designed to operate at a constant input voltage level with some tolerance. Radical voltage

variations on a power system are indicative of a system malfunction. Protective relays that monitor

system voltage and provide an output signal when the voltage goes outside predetermined limits, find a

variety of applications. Some of these applications include motor and transformer protection, interface

protection for cogeneration systems, and supervision of automatic transfer switching schemes.

Motor Protection

When selecting the type of protection for motor applications, the motor type, voltage rating, horsepower,

thermal capability during start-up, and exposure to automatic transfer restarting following a voltage

interruption need to be considered. During motor start-up, a low terminal voltage condition will inhibit the

motor from reaching rated speed. The BE1-27 Undervoltage Relay will detect this low voltage condition

and trip. Critical applications requiring continuous motor operation and applications where overloads

during start-up may be maintained for a given time period, usually have a definite time or inverse time

delay characteristic incorporated to avoid unnecessary tripping during low voltage dips. If the

undervoltage condition persists for the established time delay, the relay output contacts are connected to

the station alarm annunciator panel, allowing the station operator to take corrective action. The BE1-59

Overvoltage Relay is applied to insure the voltage does not exceed the limits established by the machine

manufacturer for proper operation. Overvoltage conditions stress the insulation level of the equipment and

may cause a dielectric breakdown resulting in a flash over to ground.

Automatic Transfer Switching

Distribution substations are sometimes designed with duplicate supply circuits and transformers to

eliminate service interruptions due to faults located on the primary feeder. In order to restore service

within a given acceptable time period, automatic transfer switching can be applied to initiate the throw

over from primary power to the alternate power source. The BE1-27 Undervoltage Relay can initiate

switching after a given time delay to void transfer switching during temporary low voltage conditions. To

return the substation to normal service upon the restoration of primary voltage, the BE1-59 Overvoltage

Relay supervises the transition to its normal operating condition.

Cogeneration

Utilities employ the use of a voltage check scheme to supervise reclosing at the substation when

cogenerators are connected to a radial distribution feeder and the cogenerator is capable of supplying the

entire load when the utility circuit breaker is open. During a faulted condition, the utility requires the

cogenerator to be disconnected from the system before reclosing the utility breaker. If the cogenerator is

connected to the system, the utility will reclose to an energized line.
This could result in reconnecting two systems out of synchronism with each other. A BE1-27

Undervoltage Relay monitoring the line voltage will inhibit reclosing of the utility circuit breaker if the

cogenerator energizes the line.
At the interface between the utility and the cogenerator, overvoltage and undervoltage relays are installed

as minimum protection to provide an operating voltage window for the cogenerator. During faulted

conditions, when the cogenerator may become overloaded, the BE1-27 Undervoltage Relay will detect

the decline in voltage and remove the cogenerator from the system. The BE1-59 Overvoltage Relay will

protect the system from overvoltage conditions that occur when power factor correction capacitors are

located on the feeder.

Advertising
This manual is related to the following products: