2-2

BE1-79M Human-Machine Interface

9170100990 Rev N

Table 2-1. BE1-79M Controls and Indicators (Refer to Figure 2-1)

Locator

Control or Indicator

Function

A

RECLOSE TIME

Controls (1, 2, 3)

Establish reclose time delays for corresponding time-

delayed reclosure attempts. Individually thumbwheel

adjustable from 00.1 to 99.9 seconds in 00.1 second

increments or if reclose time delay option is A7, second and

third RECLOSE TIME thumbwheels are adjustable from

001 to 999 seconds in one second increments. A setting of

000 on a RECLOSE TIME thumbwheel indicates the

reclosing attempt is not desired and sends the relay to

lockout at this point in the reclosing sequence.

B

RESET Control

Establishes automatic reset interval. Thumbwheel

adjustable from 10 to 1000 seconds in 10 second

increments. Optionally adjustable from 1 to 100 seconds in

1 second increments. A setting of 00 indicates a reset time

of 1000 seconds or optionally, 100 seconds.

C

RESET Switch

Momentary toggle switch, which extinguishes STATUS

LEDs (except LOCKOUT). Accessible by linkage, which

extends through bottom of front cover.

D

RESET LED

ON when relay is in RESET.

E

PILOT or RESET INHIBIT

LED (Optional)

With

PILOT option, LED is ON when pilot output relay coil

is energized. Remains ON until activation of manual

RESET lever, power loss, or when relay reaches RESET if

STATUS LED reset is optionally selected by logic switch

S23. With

RESET INHIBIT option, LED is ON when reset

inhibit input is closed.

F

POWER LED

ON when the power supply is delivering a nominal ±12 Vdc

to internal circuitry.

G

OUTPUT ENERGIZE LED

ON when reclose output relay coil is energized.

H

RELAY FAIL LED

ON when relay is not operable. Also ON during power-up

sequence.

I

STATUS LEDs

(

INST., 1, 2, 3)

(LOCKOUT)

Latched ON to indicate progression of reclosing sequence.

Extinguished by RESET lever, power loss, or when relay

reaches RESET if STATUS LED reset is optionally

selected by logic switch S23.

ON when relay is in LOCKOUT. (Non-latching.)

J

INSTANTANEOUS TRIP

(Optional)

Five toggle switches, which enable or block instantaneous

tripping of circuit breaker. Numbers correspond to the relay

state or a specific trip depending on the type of reclosing

sequence in progress.

K

RECLOSE FAIL LED

(Optional)

ON when circuit breaker 52b contact does not open within

selected time after reclose output has been energized.

L

RECLOSE FAIL Control

(Optional)

Limits duration of reclose command signal. Thumbwheel

adjustable from 0.1 to 9.9 seconds in 0.1 second

increments. For a setting of 00, the reclose command

signal is continuous until the breaker closes.

M

MAX. CYCLE LED

(Optional)

ON when maximum cycle limit, as established by the MAX.

CYCLE control, has been exceeded.