Figure 5-1. operational test setup – Basler Electric BE1-79M User Manual

Page 56

Advertising
background image

5-2

BE1-79M Tests and Adjustments

9170100990 Rev N

Figure 5-1. Operational Test Setup


STEP 3.

If Instantaneous Trip Enable option is present in your unit, place all INSTANTANEOUS TRIP

toggle switches in the Block position. Apply relay operating power. POWER LED and RELAY

FAIL LED should light. In 60 seconds, RELAY FAIL LED should go out and RESET LED

should light. If the BLTC option is present, a continuity check should show continuity between

terminals 1 and 2. If BLTC NO option is present, a continuity check should

NOT show conti-

nuity between terminals 1 and 2.

STEP 4.

Set test timer to zero. Close RI switch (S1). If option 1 is 2 (Reclose Wait) do

NOT close RI.

Place switch S5 to the RECLOSE position (terminal 15). Press and quickly release switch S6

(K1 latch) to simulate breaker opening. The OUTPUT ENERGIZE LED should light briefly.

The INST. STATUS LED should light and stay lit. Timer should indicate 50 milliseconds or

less. The RESET LED should light in 60 seconds.

STEP 5.

Toggling the front panel RESET lever should extinguish the INST. STATUS LED.

STEP 6.

Close switch S3 (IRB). Reset the timer. Press and release switch S6 (K1 latch) to simulate

breaker opening. After a short interval, the OUTPUT ENERGIZE LED should light briefly and

the STATUS 1 LED should light. Timer should indicate 5 ±0.05 seconds. If the BLTC NC op-

tion is present, a continuity check should

NOT show continuity between terminals 1 and 2. If

BLTC NO option is present, a continuity check should show continuity between terminals 1

and 2.

STEP 7.

Reset the timer. Press and release switch S6 (K1 latch) to simulate breaker opening. After a

short interval, the OUTPUT ENERGIZE LED should light briefly and the STATUS 2 LED

should light. Timer should indicate 10 ±0.1 seconds.

STEP 8.

Reset the timer. Press and release switch S6 (K1 latch). After a short interval, the OUTPUT

ENERGIZE LED should light briefly and the STATUS 3 LED should light. Timer should indi-

cate 15 ±0.15 seconds.