BE1-79M Installation

4-1

SECTION 4 • INSTALLATION

General

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to

prevent damage during transit. Immediately upon receipt of a relay, check the model and style number

against the requisition and packing list to see that they agree. Visually inspect the relay for damage that

may have occurred during shipment. If there is evidence of damage, immediately file a claim with the

carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric, High-

land, Illinois.
In the event the relay is not to be installed immediately, store the relay in its original shipping carton in a

moisture and dust free environment. When the relay is to be placed in service, it is recommended that the

operational test procedure (Section 5) be performed prior to installation.

Relay Operating Precautions

Before installation or operation of the relay, note the following precautions:

1. The relay is a solid-state device. If a wiring insulation test is required, remove the connection

plugs and withdraw the cradle from its case.

2. When the connection plugs are removed, the relay is disconnected from the operating circuit and

will not provide system protection. Always be sure that external operating (monitored) conditions

are stable before removing a relay for inspection, test, or service.

3. Be sure the relay case is hard wired to earth ground using the ground terminal on the rear of the

unit. It is recommended to use a separate ground lead to the ground bus for each relay.

Dielectric Test

In accordance with IEC 255-5 and ANSI/IEEE C37.90-1989, one-minute dielectric (high potential) tests up

to 2500 Vac (45-65 Hz) may be performed except across open contacts, which may be tested up to 1,500

Vac. Note that this device employs decoupling capacitors to ground from terminals 3, 4, 5, 6, 7, 8, 9, and

10. At 2500 Vac, a leakage current of approximately 5 mA per terminal is to be expected.

Mounting

Because the relay is of solid-state design, it does not have to be mounted vertically. Any convenient

mounting angle may be chosen. Relay outline dimensions and panel drilling diagrams are shown in

Figures 4-1 through 4-7.