RDP-110 electrical and physical characteristics are listed in the following paragraphs.

Control Power

DC Input
Range:

8 to 32 Vdc

Burden:

2 W maximum

AC Input
Range:

84 to 144 Vac

Burden:

5 VA maximum

Communication

The RDP-110 communicates through a serial, RS-485 port terminated with a 100

Ω resistor.

Audible Alarm

Frequency:

2,900 Hz, ±500 Hz

Sound Level:

90 dB(A) at 24 in (61 cm)

Temperature

Operating Temperature Range:

–40 to 70

°C (–40 to 158°F)

Storage Temperature Range:

–40 to 85

°C (–40 to 185°F)

Weight

3 kg (6.6 lb)

Type Test Data

Dielectric Strength

Withstood 1,800 Vdc for 1 minute between chassis ground and ac control power input. Withstood 700 Vdc
for 1 minute between any combination of the following circuit groups:

Chassis ground

DC control power input and RS-485 terminals

AC control power input

Radio Frequency Interference

Tested using a 5 W, handheld transceiver operating at random frequencies centered around 144 MHz
and 440 MHz with the antenna located within 6 inches (15 centimeters) of the device in both the vertical
and horizontal planes.