Testing

A built-in test mode enables field testing of RDP-110 operation.

Test Equipment and Setup

Equipment needed for testing RDP-110 operation is listed below. Connections for the test are illustrated
in Figure 9.

Power supply, 24 Vdc

Power source, 100/120 Vac, 50/60 Hz

Fuse, 1 ampere (2)

Signal generator, 10 Hz, square wave, 5 volts peak-to-peak

Figure 9. RDP-110 Test Setup

Test Procedure

1.

Connect the RDP-110 test setup as shown in Figure 9.

2.

Apply 24 Vdc control power. The Display Panel On LED should light.

3.

Press and hold the Lamp Test pushbutton. All LEDs should light and the horn should sound.

4.

Release the Lamp Test pushbutton to reset the indicators and horn.

5.

Apply the 10 Hz signal.

6.

Press and release the Lamp Test pushbutton. Observe that the LEDs and horn annunciate in the
eighteen-step sequence indicated in Figure 10. This sequence will repeat until the Alarm Silence
pushbutton is operated.

7.

Press and release the Alarm Silence to end the annunciation sequence.

8.

Remove the 10 Hz signal and 24 Vdc control power.

9.

Repeat the test with 100/120 Vac control power applied instead of 24 Vdc control power.

RDP-110

1BTesting