BRONKHORST

®

 

Page 22   

 

 

 

 

RS232 interface   

 

 

 

9.17.027 

N

0A  Parameter number (FBnr.) 10

Init mode

30 

52 

01010010

Parameter value 82, reset init mode

31 

\r 

Carriage Return 

End 

32 

\n 

Line Feed 

Total String 

:1D0301800A4081C500000000C63F800000C7000000004800000000000A52\r\n 

 

Answer by node 3

Nr 

Byte 

Description 

Description per block

Start character 

Start 

04 

Fixed message length 4.

03 

Node address 

00 

Command status 

00 

Status ok. 

Status 

1C 

Status ok, value points to end of send message.

\r 

Carriage Return 

End 

\n 

Line Feed 

Total String 

:040300001C\r\n 

 

3.10.3 Request setpoint 

 

Request setpoint from node 3 process 1, type integer.

Nr  Byte 

Layout 

Description 

Description per block 

 

 

Start 

06 

 

Length 6 

03 

 

Node 3 

04 

 

Command read 

01 

00000001 

00  Process not chained (return)

Process 1 

01  Process 1 (return)

21 

00100001 

00  Parameter not chained (return)

Parameter index 1 

Process 1 

Parameter number 1 

Setpoint 

20  Parameter type ‘integer’ (return)

01  Parameter index 1 (return)

01 

00000001 

01  Process 1

21 

00100001 

20  Parameter type ‘integer’

01  Parameter number (FBnr.) 1 (setpoint)

\r 

 

 

 

Carriage Return

End 

\n 

 

 

 

Line Feed

Total String 

:06030401210121\r\n

 

Answer from node 3 process 1, type integer. 

Nr  Byte 

Layout 

Description 

Description per block 

 

 

Start 

06 

 

Length 6 

03 

 

Node 3 

02 

 

Command write 

01 

00000001 

00  Process not chained 

Process 

01  Process 1 (receiving process)

21 

00100001 

00  Parameter not chained

Parameter index 1 

Setpoint 

20  Parameter type ‘integer’

01  Parameter index 1

Advertising