4 DUAL INTERFACE OPERATION 

 
When operating a controller (reading measured value and sending setpoint) for proper operation it is important that 
the controller gets its setpoint from the right source. Setpoints may come from different sources: analog input, field 
bus interface or RS232 or may be overruled by close valve or open valve (purge) commands. Therefore it is important 
to know what the setpoint source of the controller is. This can be set by means of parameter control mode (process 1, 
parameter 4). 
 
In some cases it is possible that the setpoints may come from 2 sources at the same time. The last send setpoint will 
be valid and send to the controller. This is the case in control mode = 0, when setpoints may come through any field 
bus interface or RS232. 
 
However, there could be situations where control over the instrument seems impossible. This is the case when the 
instrument  comes  into  a  safe‐state  e.g.  when  field  bus  communication  is  disturbed  or  disconnected.  Valve  will  be 
forced to a safe state automatically: closed (NC) or fully open (NO). 
 
In case you want to get control back via RS232 operation, you have to change the control mode. When control mode 
gets value 18, safe state will be overruled and sending setpoints via RS232 interface will have effect on the controller 
again. 
 

 

See also document nr. 9.17.023 for more detailed description about digital instrument parameters and 
their behaviour. 

http://www.bronkhorst.com/en/downloads/instruction_manuals/

 