Operation – Flowserve OR 52-5 User Manual

Page 29

Advertising
background image

29

Operation

Start

Apply power.
The 7-segment display shows briefly the version number
of the software.
Then the indicator counts until the actual value is
reached.
The LED ppm is illuminated.

Alarm 1 and 2

When the limit value for alarm 1 or 2 is exceeded the
adjusted time delay is activated. The LED alarm 1 or
LED alarm 2 is flashing.
After the time delay has elapsed LED alarm 1 or LED
alarm 2 will light up.
The relay contact for alarm 1 or 2 opens.

ALARM

1

2

ppm

sec

cal

0

OIL

ALARM

1

2

ppm

sec

cal

0

OIL

Note

When the limit values are exceeded the measuring transducer will not

interlock automatically. If the installation requires a lockout function, the
latter must be implemented in the sequence circuit (burner protection
circuit). This circuit must comply with the requirements of the DIN VDE
0116 regulations.

Advertising
This manual is related to the following products: