18

c

DANGER: When operating using RE-CAL or local control, the valve

will not respond to external commands. Notify proper personnel

that the valve will not respond to remote command changes, and

make sure the valve is properly isolated.

7.6 Manual Jog Calibration Operation

If the Quick Calibration switch is set to Jog, the calibration will initially
close the valve then cause a small jump in the valve position. The jog
calibration process will only allow the user to manually set the span;
zero position is automatically always set at the seat. If an elevated
zero is needed a handheld or other PC-based configuration software
is required. When performing a jog calibration, the LEDs will flash in
a sequence of Y-G-Y-Y (yellow-green-yellow-yellow) which indicates
that the user must use the Jog buttons (▲ and ▼) to manually
position the valve to the 100% position. When the stem is properly
positioned press both the Jog buttons (▲ and ▼) simultaneously
again to register the 100% position and proceed. No more user
actions are required while the calibration process is completed.
When the lights return to a sequence that starts with a green light the
calibration is complete. An explanation of the various light sequences
follows.

7.7 Local Control of Valve Position

Local control of valve position can be achieved from the user
interface by holding down both Jog buttons and the RE-CAL button
simultaneously for three seconds. While in this mode the LEDs will
flash a Y-G-Y-Y (yellow- green-yellow-yellow) sequence. Use the
two Jog buttons (▲ and ▼) to manually control the position of the
valve. To exit the local control mode and return to normal operation,
briefly press the RE-CAL button.

7.8 Factory Reset

To perform a factory reset, disconnect power, hold the RE-CAL button
down, and reconnect power. Performing a factory reset will cause all
of the internal variables, including calibration, to be reset to factory
defaults. The positioner must be recalibrated after a factory reset.
User configured limits, alarm settings, and valve information will also
need to be restored.

c

DANGER: Performing a factory reset may result in the inability

to operate the valve until reconfigured properly. Notify proper

personnel that the valve may stroke, and make sure the valve is

properly isolated.

7.9 Logix 3400MD Status Condition

The blink codes used to convey the status of the Logix 3400MD
digital positioner are described in the table below. In general,
any sequence starting with a green light flashing first is a normal
operating mode and indicates that there are no internal problems. Any
sequence starting with a yellow light flashing indicates that the unit
is in a special calibration or test mode, or that there was a calibration
problem. Any sequence starting with a red light flashing indicates
that there is an operational problem with the unit.

Code

Meaning

Error
Code

Sticker

Line

Sticker Text

GGGG

Normal Operation

255

1

Normal Operation

GGGY

MPC Active

13

2

Tight shutoff (MPC)

active*

GGYG

Local Interface

Disabled

14

3

Local Interface

Disabled*

GGYY

Digital Command

Mode

2

4

Digital Command

mode*

GGRR

Squawk Mode

3

5

Squawk mode*

GYGG

Position Upper

Limit

11

6

Upper or lower

position alert*

GYGG

Position Lower

Limit

12

GYGY

Soft Stop Upper

Limit

9

7

Soft stop position

reached*

GYGY

Soft Stop Lower

Limit

10

GRGG

Valve Cycles

Warning

22

8

Travel or cycle limit

reached*

GRGG

Valve Travel

Warning

23

GRGG

Spool Cycles

Warning

50

GRGG

Spol Travel

Warning

51

YGGY

Signature in

Progress

5

9

Signature in

progress

YGGR

Initializing

0

10

Initialization in

progress

YGYG

Stroke Cal in

Progress

24

11

Calibration in

progress

YGYG

Command Loop

Cal in Progress

25

YGYG

Pressure Cal in

Progress

26

YGYG

Analog Output

Cal in

Progress

27

YGYG

Setting Inner

Loop Offset

28

YGYY

Joc Command

Mode

4

12

Local jog command

mode

YGYR

Jog Calibration

Set 100

Position

62

13

Jog cal waiting ->

Set 100% pos.

Table 9: Status and Conditions