Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ –5/15

8

Table 7: Hazardous Locations Information

ATEX

Flame Proof
FM07ATEX0005X

II 2 G

Ex d IIB+H2 T4/T6 Gb IP65

T4 Ta = -52˚C to +80˚C

T6 Ta = -52˚C to +60˚C

II 2 D

Ex tD A21 IP65 T95˚C Db

Ta = -52˚C to +55C

Intrinsically Safe
FM07ATEX0029X

II 1 G

Ex ia IIC T4/T6

T4 Ta = -40˚C to +80˚C

T6 Ta = -40˚C to +40˚C

Entity Parameters
Fisco Field Device

Vmax = 24V

Imax = 380mA

Pi = 5.32W

Ci = 3.3nF

Li = 1uH

North America (FM/CSA)

Explosion Proof
Class I, Div 1, Groups B,C,D T6

DIP Class II, III, Div 1 Groups E,F,G T6

T6 Ta = -40˚C to +60˚C (FM US)

T4 Ta = -55˚C to +80˚C (CSA)

T5 Ta = -55˚C to +60˚C (CSA)

Type 4/4X IP65

Class 1, Zone 1, AEx d IIB+H2 T6 (FM US)

T6 Ta = -40˚C to +60˚C (FM US)

Type 4/4X IP65

Class 1, Zone 1, Ex d IIB+H2 T4/T6 (CSA)

T4 Ta = -55˚C to +80˚C

T6 Ta = -55˚C to +60˚C

Type 4/4X IP65
Intrinsically Safe
Class I,II, III, Div 1, Groups A,B,C,D,E,F,G T4/T6

Class I, Zone 0, AExia IIC T4/T6 (FM US)

Class I, Zone 0, Ex ia IIC T4/T6 (CSA)

T4 (Ta = -40˚C to +80˚C)

T6 (Ta = -40˚C to +40˚C)

Type 4/4X IP65

Entity Parameters

Fisco Field Device

Vmax = 24V

Imax = 380mA

Pi = 5.32W

Ci = 3.3nF

Li = 1uH

InMetro

Explosion Proof
TÜV 12.0646

Ex d IIB+H2 T5 Gb IP65

Ta = -55˚C to +80˚C

Ex tb IIIC T95C Db IP65

Ta = -55C to +55C
Intrinsically Safe
TÜV 12.0605
Ex ia IIC T4 Ga IP65
T4 Ta = -40˚C to +60˚C
Entity Parameters
Fisco Field Device

Vmax = 24V

Imax = 380mA

Pi = 5.32W

Ci = 3.3nF

Li = 1uH

Special Conditions for Safe Use:

1. When used within a Zone 0 location, cast-aluminum (when Enclosure Option b = 0, 2, 3, 4,or 5) enclosures shall be installed in such manner as to prevent the possibility of sparks resulting from

friction or impact against the enclosure.

2. To prevent the risk of electrostatic sparking, the equipment’s mechanical pressure gauges shall be cleaned only with a damp cloth.

3. Using the box provided on the nameplate, the user shall permanently mark the protection type chosen for the specific installation. Once the type of protection has been marked it shall not be

changed.

4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.

Gost

TR CU

Ex d IIB+H2 T4/T6 Gb IP65

Ex ia IIC T4/T6 Ga IP65

Ex nL nA IIC T6

T4 (Ta = -52˚C to +80˚C)

T6 (Ta = -52˚C to +60˚C)

Ex tb IIIC T95C Db IP65

IECEx

Explosion Proof
IECEx FMG 11.0002X

Ex d IIB+H2 T4/T6 Gb IP65

T4 Ta = -52˚C to +80˚C

T6 Ta = -52˚C to +60˚C

Ex tb IIIC T95C Db

Ta = -52C to +55C
Intrinsically Safe
IECEx FME 07.0001X

Ex ia IIC T4/T6 Ga IP65

T4 Ta = -40˚C to +80˚C

T6 Ta = -40˚C to +40˚C
Entity Parameters
Fisco Field Device

Vmax = 24V

Imax = 380mA

Pi = 5.32W

Ci = 3.3nF

Li = 1uH

Advertising