ports 1 and 2. The main PCB electronics automatically senses
the presence of the pressure sensor board. If present, the actuator
pressure sensors are used in the positioner control algorithm to
enhance valve stability. For optimal performance, the actuator
pressure sensors need to be calibrated. The actuator pressure sensor
calibration is performed using a 375 Handheld Communicator or Host
configuration software.

In the standard model, the pressure sensor board is replaced by a
plate that plugs the actuator pressure sensor ports. This plate can
be replaced by a pressure sensor board to field-upgrade a standard
model to an advanced model.

Removing the Pressure Sensor Board (Advanced Model)
To replace the pressure sensor board, refer to Figures 12, 16 and 21
and proceed as outlined below. The following tools are required:

• Phillips screwdriver

c

DANGER: Observe precautions for handling electrostatically

sensitive devices.

1. Make sure the valve is bypassed or in a safe condition.

2. Disconnect the power and air supply to the unit.

3. Remove the main cover.

4. Remove the plastic board cover by removing the three retaining

screws (see Figure 16).

5. Disconnect the ribbon cable on the pressure sensor board from

the PCB assembly (see Figure 12). Lifting the main board may
make this easier.

6. Remove the two screws holding the pressure sensor board to

the housing. Lift the metal stiffener plate off the pressure sensor
board and set aside for future use.

7. Remove the pressure sensor board.

Removing the Pressure Sensor Plug Plate (Standard Model)
To upgrade a standard model to an advanced model, the pressure
sensor plug plate must be removed and replaced by a pressure
sensor board. The main PCB electronics automatically senses the
presence of the pressure sensor board. If present, the actuator
pressure sensors are used in the positioner control algorithm to
enhance valve stability. For optimal performance, the actuator
pressure sensors need to be calibrated. The actuator pressure sensor
calibration is performed using a Handheld Communicator or host
configuration software.

To upgrade a standard model to an advanced model, refer to Figures
12, 16 and 21 and proceed as outlined below. The following tools are
required:

• Phillips screwdriver
1. Make sure the valve is bypassed or in a safe condition.

2. Disconnect the power and air supply to the unit.

3. Remove the main cover.

4. Remove the plastic board cover by removing the three retaining

screws (see Figure 16).

5. Remove the two screws holding the pressure sensor plug plate

to the housing. Lift the metal stiffener plate off the pressure
sensor plug plate and set aside for future use.

6. Remove the pressure sensor plug plate and discard.

Installing the Pressure Sensor Board (Advanced Model)
The pressure sensor board is installed on the advanced model only.
To install the pressure sensor board, refer to Figures 12, 16 and 22
and proceed as outlined below. The following tools are required:

• Phillips screwdriver
• Torque wrench

c

DANGER: Observe precautions for handling electrostatically sensi-

tive devices.

1. Verify that the two pressure sensor O-rings (item 15) are in place

in the housing.

2. Set the pressure sensor board assembly in place so that the

O-rings make contact with the faces of the pressure sensors.

3. Place the metal stiffener plate (item 12) on top of the pressure

sensor board over the pressure sensors and align the two holes
in the pressure sensor plate with the threaded bosses in the
housing.

4. Insert two screws through the stiffener plate and pressure sensor

board into the threaded holes in the housing and tighten evenly, to
8 in-lb.

5. Connect the ribbon cable on the pressure sensor board to the

main PCB assembly.

6. Install the plastic board cover. Insert the three retaining screws

through the plastic cover into the threaded boss and tighten
evenly, using a Phillips screwdriver. Do not overtighten.

7. Reinstall all covers.

8. Reconnect power and air supply to the positioner. Use the Host

software or a handheld communicator to perform a pressure
sensor calibration.

8.9 User Interface Board

The user interface board provides a connection point inside the
explosion-proof housing for all hookups to the positioner.