42

6. Place spool valve shroud onto spool valve cover.

7. Place the spool valve cover assembly in place by setting it on the

ramp and sliding it until the tab seats in the slot (Figures 13 and
18) and secure with a 8-32 screw.

8.6 Stem Position Sensor

The position feedback assembly transmits valve positions information
to the processor. This is accomplished by means of a rotary position
sensor that connects to the valve stem through a feedback linkage. To
provide for accurate tracking of the pin in the slot, the follower arm
is biased against one side of the slot with a rotary spring. This spring
also automatically moves the position feedback assembly to its limit
in the unlikely event of failure of any component in the linkage.

Stem Position Sensor Replacement
To replace the stem position sensor, refer to Figure 16, 19 and 22 and
proceed as outlined below. The following tools are required:

• Phillips screwdriver

c

DANGER: Observe precautions for handling electrostatically sensi-

tive devices.

1. Make sure the valve is bypassed or in a safe condition.

2. Disconnect the power and air supply to the unit.

3. Remove the main cover.

4. Remove the plastic board cover by removing the three retaining

screws (see Figure 16).

5. Disconnect the position sensor wires from the main PCB

assembly.

6. Remove the two rotary position sensor-retaining screws and lift

the sensor out of the housing.

7. Turn the new position sensor shaft until the dot on the side of the

shaft is aligned with the wires on the side of the position sensor
(Figure 19).

8. Insert the position sensor into the shaft with the wires pointing

toward the main PCB assembly. Turn the position sensor clock-
wise until bolting slots align with the housing screw holes and the
wires on the sensor protrude over the main PCB assembly.

NOTE: Do not mix the position sensor with those from older Logix
positioners. Older models contain sensors with different ranges that
will not work in the Logix 3400MD model. The wires on the Logix
3400MD position sensor are red, white and black.

9. Carefully center the position sensor on the shaft bore, insert and

tighten the screws. Do not overtighten.

10. Route the wires along the side of the position sensor and recon-

nect to the main PCB assembly.

11. Install the plastic board cover. Insert the three retaining screws

through the plastic cover into the threaded boss and tighten
evenly, using a Phillips screwdriver. Do not overtighten (see
Figure 16).

12. Reinstall all covers.

13. Reconnect power and air supply to the positioner and perform a

stroke calibration.

8.7 Main PCB Assembly

The main printed circuit board (PCB) assembly contains the
circuit boards and processors that perform control functions of
the positioner. The main PCB is to be replaced as a unit. None of
the components on the main PCB are serviceable. It consists of a
controller board and a Fieldbus communication board.

Replacing Main PCB Assembly
To replace the main PCB assembly, refer to Figure 12 and 16 and
proceed as outlined below. The following tools are required:

• Phillips screwdriver

c

DANGER: Observe precautions for handling electrostatically sensi-

tive devices.

1. Make sure the valve is bypassed or in a safe condition.

2. Disconnect the power and air supply to the unit.

3. Remove the main cover.

4. Remove the plastic board cover by removing the three retaining

screws (see Figure 16).

5. Remove the retaining screw from the main PCB assembly.

6. Remove the five wire connections from the main PCB assembly

and lift the main PCB out of the housing (see Figure 16).

7. Reinstall the five wire connections (see Figure 12) on the new

main PCB.

8. Install the new main PCB into the housing. Insert the retaining

screw through the board into the threaded boss and tighten,
using a Phillips screwdriver. Do not over tighten.

9. Install the plastic board cover. Insert the three retaining screws

through the plastic cover into the threaded boss and tighten
evenly, using a Phillips screwdriver. Do not overtighten (see
Figure 16).

10. Reinstall all covers.

11. Reconnect power and air supply to the positioner and reconfigure

8.8 Pressure Sensor Board

On advanced model Logix 3400MD positioners, a pressure sensor
board is installed in the positioner. The pressure sensor board
contains two pressure sensors that measure the pressure on output

Advertising