8.3 Checking or Setting Internal

Regulator Pressure

To check or set the internal regulator pressure, refer to Figure 17
and proceed as outlined below. The tools and equipment used in the
next procedure are from indicated vendors. The following tools are
required:

• Calibrated pressure gauge (0 to 30 psi)

1

16

” flexible tubing

• Barbed tee (Clippard Minimatic part number T22-2 or equivalent)

3

32

” Allen wrench

3

8

” open-end wrench

c

DANGER: Observe precautions for handling electrostatically

sensitive devices.

Figure 19: Stem Position

Sensor Orientation

Figure 18: Spool Valve

Cover Assembly

1. Make sure the valve is bypassed or in a safe condition.

2. Remove the main cover.

3. Remove the plastic board cover by removing the three retaining

screws.

4. Remove the 1⁄16” flexible tubing from the barbed fitting on the

side of the driver module.

5. Obtain a barbed tee and two pieces of 1⁄16” flexible tubing, a few

inches in length each.