GAI-Tronics LE200-RM Rack-Mount Page/Party Line Extender User Manual

Page 35

Advertising
background image

Pub. 42004-392G

M

ODEL

LE200-RM

R

ACK

-M

OUNT

P

AGE

/P

ARTY

®

L

INE

E

XTENDER

P

AGE

33 of 56

e:\standard ioms - current release\42004 instr. manuals\42004-392g.doc
09/14

Terminal Designator

Description

TB5 (Bottom)

N.C.

Output 5 – contact #2

COM

N.O.

TB6 (Top)

N.C.

Page line audio – contact #1

COM

N.O.

TB6 (Bottom)

N.C.

Page line audio – contact #2

COM

N.O.

TB7 (Top)

N.C.

Page line ground fault – contact #1

COM

N.O.

TB7 (Bottom)

N.C.

Page line ground fault – contact #2

COM

N.O.

Page Line Audio Monitoring Connections

The Model LE200-RM provides a balanced 600-ohm audio output for monitoring audio on both the local
and remote page lines. Connect any external audio input device (audio recorder, radio transmitter,
amplifier, etc.) to the audio line monitoring terminals using a twisted pair cable. The input impedance of
the audio device should be 600 ohms or greater. Terminals are located at connector P16 on the Main
PCBA and are labeled as shown below.

Table 31.

Terminal Designator Description

P16-1

PG MON L2

Page line monitor audio output (L2)

P16-2

− No

connection

P16-3

PG MON L1

Page line monitor audio output (L1)