H*38DF Gas Fireplace

Installation

Figure 12. H*38DF* Top Vent Venting Graph for wall mounted terminations.

The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 12 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 114" and the horizontal

run to the wall flange of the vent termination is 168", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 36" and the horizontal

run to the wall flange of the vent termination is 60", this would be

would NOT be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 60" and

the horizontal run to the wall flange of the vent termination is 144",

this would NOT be an acceptable installation.

Section 3-3-1: Venting Layout: Wall mounted termination.
Selection of components and details of venting layout should adhere

to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield requirements see Section 3-3-3.

„

Once the proposed venting layout has been determined refer

to Figure 12, 12a, or 15 to ensure the layout is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All measurements for vertical or horizontal runs are measured

from centre of the vent pipe.

„

Venting runs must fall within the limits set by the venting graph,

see Figure 12 or 12a.

Figure 12a. Top Vented, wall mounted installation with one 90° bend. The vent

run must comply with Venting Graph for Top vent, wall mounted terminations,

Figure 12 or .

Figure 13a. Top Vented, wall mounted Multi-elbow installation. See Venting

Graph for Top vent, wall mounted terminations, Figure 12 or 12a.

Figure 13. H38DFN ONLY Top Vent Venting Graph for wall mounted terminations.

Solid Section

Flex Section

Hearth

150” Max.

Heat

Shield

Termination

Exterior

Wall

42”

42”

A

C

B

If your installation does not fall within

the venting graph para- meters,

please contact a local Montigo dealer

for Power Venting options.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

72”

42”

A

C

B

If your installation does not fall within the venting

graph parameters, please contact a local Montigo

dealer for Power Venting options.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

Heat

Shield

Termination

Hearth

Exterior

Wall

42”Min.

Max. as per graph

Flex or Rigid

Section