Installation – Montigo H38DF User Manual

Page 16

Advertising
background image

Page 16

XG0147 - 150204.1

H*38DF Gas Fireplace

Installation

Figure 16a. H*38DF* Rear Vented, wall mounted Multi-elbow termination

installation. The vent run must comply with the Venting Graph for Rear vent,

wall mounted terminations, Figure 15.

Figure 16. Straight run, Rear Vented, wall mounted termination for H*38DF*,

Figure 15.

30” Max.

52” Min.

18”

Max.

Flex or Rigid

Section

23 1/4”

Min.

28 3/4”

28 3/4”

PXT Extension

RHS101 Heat

Shield

Termination

Hearth

Exterior

Wall

NOTE:

18” MAX. horizontal

run with no vertical lift.

18” MAX.

28 3/4”

18”

A

B

C

52”

48”

Figure 15. Rear Vent Venting Graph for wall mounted terminations.

If your installation does not fall

within the venting graph parame-

ters, please contact a local Montigo

Dealer for Power Venting options.

Notes Wall Mounted Terminations: REAR VENT

„

All dimension lengths for vertical or horizontal runs are measured

from centre of the vent pipe.

„

Venting runs must fall within the limits set by the venting graphs,

see Figure 15.

„

Fireplace must be converted to Rear Vent configuration prior to

running vent, see Figure 8 and 8a.

The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the horizontal

run to the wall flange of the vent termination is 138", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 48" and the horizontal

run to the wall flange of the vent termination is 96", this would NOT

be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and

the horizontal run to the wall flange of the vent termination is 120",

this would NOT be an acceptable installation.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

Note: Images are shown without screens for clarity purposes. However,

your fireplace should not be operated without proper installation of

screens.