Installation

Figure 9. Top vent, Roof mounted termination with no offset in vent

run.

Roof mounted Terminations
The following details are some possible configurations for Roof

mounted terminations.

Section 3-2:

Installing a Roof Mounted Direct Vent

Termination (PVTK-1)
This section applies to installations where the direct vent termi-

nation will be roof mounted.

Section 3-2-1:

VENTING LAYOUT

Selection of components and details of venting lay out should

adhere to the following guidelines:

„

The maximum termination point is 32’ above the fireplace.

(NOTE: if the maximum termination height is used, the flame

pattern may be affected).

„

The Vertical termination must be a minimum 2’ higher

than where the termination exits the roofing materials,

(asphalt shingles, cedar shakes, etc). This distance should

be measured from the high side of the roof slope where the

flue flashing intersects the roofing materials. (see Figures

9 - 9c).

„

For a detailed diagram of allowed termination locations, see

Appendix A.

„

Termination location must be a minimum 6’ from a mechanical

air inlet.

„

A maximum of two offsets (each offset is made up of 2-90°

bends) may be made for vertical vent runs.

„

Firestops must be installed as required by National & local

codes.

„

Ensure all horizontal runs are supported with a minimum of 3

supports per 10’ of venting.

„

Install all roof flashing and storm collars as shown.

PVTK1 Termination

PEXT

PEXT-10

Adaptor

Flue

Collar

Figure 9a. Top vent, Roof mounted with 1 offset (1 offset= two 90°

bends).

Figure 9b. Top vent, Roof mounted with 2 offsets (1 offset= two 90°

bends).

PVTK1 Termination

PVTK1 Termination