Installation, Rear vent venting runs, Reduced vertical installation – Montigo C34DV User Manual

Page 10

Advertising
background image

Page 10

C-Series DV Gas Fireplace

Part No. XG0170 - 080610

Installation

Figure 20. Corner installation.

Figure 21. Flex installation.

2. 45° Corner Installation.
Attach an PEL-45 (45° elbow) directly onto the flue collar. Cut the

PXT-20 to suit, and attach it to the PEL-45. Slide the fireplace into

position and attach to the termination. Maximum horizontal run

must not exceed 20"

3. Corner Installation — 45° or less.
Use an PTO-3 or PTO-3F termination, an PFL-1 or PFL-2(12" or 24"

compressed length) and a frame, if appropriate. Flex may be turned to

obtain desired degree of angle required but must not exceed 45°.

Figure 19. Extended installation.

Rear Vent Venting Runs

A. No Lift Installations

The C-Series DV Rear Vent has three possible installations which do

not require vertical lift.

1. Straight Installation.
The C-Series DV rear vent versions are supplied with and 18"

extension pipe (PXT-20) with female/female connections. For shorter

installations, cut the PXT-20 to the desired length. Refer to page 4

for measurements from the hearth to the center of the termination.

Note:

For Rear Vent models, maximum horizontal run with no

vertical lift must never exceed 20".

Figure 18. Reducing Vertical Vent from 5/8" to 4/7".

Reduced Vertical Installation

It is possible to reduce vertical vent runs from 5"/8" venting to 4"/7"

venting. Reduced vertical venting may only be used when the installation

exceeds 12 feet and terminates through the roof, and if the vertical vent

reducer is used with the following venting configuration.

PXT-20

PEL-45

PXT-20