Installation – Montigo C34DV User Manual

Page 8

Advertising
background image

Page 8

C-Series DV Gas Fireplace

Part No. XG0170 - 080610

PEL

Example 1:
For our shortest venting configuration use components A and E (see

table on page 6).

Figure 10. Typical Top Vent installation. If the 90° elbow is installed

directly on the fireplace, for height to the center of the
termination see chart on page 4.

Horizontal Venting

Figure 11. Typical Top Vent installation. The solid sections can be used in

various combinations to obtain the desired vent run. The vent
run
must fall within the limits set by the venting graph.

90° Elbow

PEXT Section

Termination

Figure 12. Extended Installation using a combination of solid and flex

venting. Use the vent graph to determine your allowable
run, then select appropriate components.

Figure 13. Retracted Installation using a combination of solid and flex

venting. Use the vent graph to determine your allowable
run, then select appropriate components.

Figure 14. Horizontal flex installation with no vertical rise.

Installation

PEL-90F/F Elbow

Example 2:
Rigid sections and an elbow used in conjunction with 3 ft. flex section

(MFL-3) will, when extended in a five foot chase, allow for a maximum

horizontal run of twelve and one-half feet from the centre of the fireplace

to outside wall and a minimum of 7'6" when retracted in opposite direction

(see Figure 12 & 13).
"C" flex sections and "D" rigid sections may be used in conjunction with

one another to obtain different possible horizontal length installations,

Figure 13.
NOTE: Flex section with no vertical rise must not exceed maximum

horizontal length of 3 feet (see Figure 14). Flex runs over 3 feet must

fall within the limits set by the venting graph, and must have a minimum

vertical rise of 3" per foot of flex.

36” max.

Flex Section

Hearth

Termination

Exterior

Wall

Advertising
This manual is related to the following products: