Maintenance

Gas Control Valve

Pilot Burner Adjustment

1. Locate Pilot Adjustment Screw. (See figure 35.)
2. Adjust pilot screw to provide properly sized flame as shown in

figure 35).

3. After installing or servicing, leak test with a soap solution with

main burner on. Coat pipe and tubing joints, gasket etc. with soap

solution. Bubbles indicate leaks. Tighten any areas where the

bubbles appear until the bubbling stops completely.

Figure 35. Pilot Burner.

Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy Pilot Flame

Locate pilot adjustment screw on

gas control valve. Flame is decreased by

turning adjustment screw clockwise.

Pilot won’t ignite

Disconnect remote wires and try to

light pilot. If pilot now works, remote

connections are faulty. Check wiring

diagram figure

31.

Main burner will

1. Check wiring (see figure 31).

not light

2. Check wall switch for proper

connection.

C-Series-DV

Troubleshooting

If your fireplace still does not operate correctly, consult your dealer or the

manufacturer.
All service and repairs should be performed by a qualified agency.
All spare parts, optional fans, and optional trim finishes are available from your

local dealer or the manufacturer.

C-Series DV-I

Figure 33. SIT gas valve.

Figure 34. IPI gas valve.

- Turn Gas Supply Off

- Set thermostat to

call for heat

SV9500 / SV9600

is powered

(24VAC nominal)

HSI

Terminals

NOTE:

Before Troubleshooting, Familiarize Yourself With

The Startup And Checkout Procedure.

START

HONEYWELL SV9500 /9600

Troublshooting Sequence

INSET

NO

CHECK:

- Line voltage power

- Low voltage transformer

- Limit Controller

- Thermostat

- Wiring

- Air proving switch on

combustion air blower system

-Vent damper (if used) is open

and end switch made

NO

NO

YES

NO

YES

Unplug Pilot Burner Cable,

Measure Voltage at

SV9500/SV9600 HSI

Terminals (24VAC

Nominal, see INSET)

Replace

SV9500/

SV9600

Igniter warms up and

glows red.

YES

YES

NO

YES

NO

Pilot Valve opens.

Replace Igniter /

Flame Rod Assembly

Replace SV9500/SV9600

NO

NO

YES

YES

Turn gas on.

Pilot Burner Lights?

Main Valve opens?

SYSTEM OK

Discard old Igniter /

Flame Rod Assembly

Measure Volume to

SV9500 / SV9600 Voltage

must be at least 19.5 VAC

Check

Transformer

Line Volt

Supply

Replace Igniter /

Flame Rod Assembly

Replace

SV9500 /

SV9600.

Save old

Igniter/ Flame

Rod Assembly

for service.

Replace Igniter / Flame

Rod Assembly and retain.

Restart troubleshooting

Sequence. Does main

valve open?

NOTE: Gas control knob cannot be turned from

"PILOT" to "OFF" unless knob is pushed

in slightly. Do not force.

Gas Control Knob

(Shown in "Pilot" postion.)

Manifold Pressure

Test Connection

Pilot Adjustment Screw

Inlet

Pressure

Power

Generator

Wall Switch