Installation, Venting runs, Installing heat guards over terminations – Montigo M38DV PFC User Manual

Page 5: Installing terminations with msr frames, Installing terminations with mosr frames, The venting graph

Advertising
background image

Page 

P/N XG0202

M38DV-PFC Peninsula Gas Fireplace

Installation

Installing Heat Guards over Terminations

1. Ensure that the two

long mounting brackets are facing the bot-

tom of the termination. (See inset). This will provide more heat
protection at the top of the termination, where temperatures are
highest.

2. Attach to the faceplate of the termination using four sheet metal

screws.

Installing Terminations with MSR Frames

1. Frame the termination opening to 12" x 12".
2. Fasten the termination to the studs using a minimum of 4 screws.

12

12

MSR

PTO-3

PTO-3F

Figure 6b.

Installing a PTKO termination with the MSR frame.

Figure 6c.

Installing a PTKO termination with the MOSR frame.

12

12

12

MOSR

PKO-3

PTO-3F

Installing Terminations with MOSR Frames

1. Frame the termination opening to 12" x 12".
2. Fasten the MSR frame to the interior side of the studs using a

minimum of 4 screws.

3. Insert the termination into the MSR frame as shown here, and

attach by screwing through the four pilot holes in the termination.

Venting Runs

If your installation requires more than 12" of horizontal venting, some
vertical lift is required. Use the vent graph below to determine an
acceptable vent run. Unacceptable venting can affect the fireplace's
combustion.

the maximum horizontal vent run is 16 feet

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting Graph
(Fig. 7) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.

0

24

48

72

96

120

144

168

192

Horizontal Run (in.)

Hearth

0

12

24

36

48

60

72

84

96

Center of Vent (28.5")

Figure 7.

Venting Graph.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 82", and the hori-
zontal run to the wall flange of the vent termination is 156", this
would be an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 72" and the horizontal
run to the wall flange of the vent termination is 36", this would be
an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 48" and
the horizontal run to the wall flange of the vent termination is
108", this would NOT be an acceptable installation.

PTKOG

Figure 6d.

Installing the heat guard.