ONICON F-5200 Inline User Manual

Page 18

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5200 Inline Thermal Mass Flow Meter Manual 05/14 - 0763-4 / 19476

Page

18

SECTION 5.0: TROUBLESHOOTING GUIDE

NOTE: Also refer to the START-UP AND COMMISSIONING GUIDE located on page 15.

REPORTED PROBLEM

POSSIBLE SOLUTIONS

No signal

• Verify that the meter is properly installed in the pipe.
• Verify that the flow direction arrow is pointing in the right direction.
• Verify supply voltage.
• Verify correct wiring to control system (see wiring diagram).
• Verify that there is flow in the pipe.
• Please contact ONICON for further assistance.

Reading is too high or
low

• Verify that the meter is properly installed in the pipe.
• Verify that the flow direction arrow is pointing in the right direction.
• Verify correct wiring to control system (see wiring diagram).
• Confirm that the control system is programmed for correct flow range

or pulse scale factor.

• Verify that the meter cable shield is connected to earth at the control

system. Lack of proper shielding can lead to excessive noise that can
affect the flow reading.

• Verify that the meter is connected to earth.
• Check for ground loop or offset voltage:
• Disconnect analog signal input from control system and measure

analog output directly from the flow meter.

• Reconnect signal input to control system and measure the analog

signal again. Any difference between these readings indicates a
potential ground loop or offset voltage.

• Meter is being used to measure flow of a different gas or gas mix than

the meter was specified and calibrated for.

• Please contact ONICON for further assistance.

Erratic readings

• Confirm that the meter is connected to earth and all cabling is

properly shielded.

• Please contact ONICON for further assistance.