3.2 MECHANICAL INSTALLATION

ONICON Insertion Thermal Mass Flow Meters are designed to allow for insertion and removal,

when necessary, without interrupting flow in the pipe. To take advantage of this feature, the flow

meter must be installed through an isolation valve. The installation must allow for sufficient

overhead clearance to fully extract the meter, and a full 5/8” opening in the pipe wall is required

to clear the sensor head and allow for insertion. Make sure that your valves and fittings are full

port and at least ¾” in actual internal diameter.

CAUTION

ONICON insertion style flow meters must be installed through a valve assembly. Failure to do so

negates the ability to remove the meter without disrupting flow. It will also result in an excessive

amount of stem protruding from the pipe. Excessive stem lengths unnecessarily expose the meter

to incidental damage.

!

3.2.1 Installation Kits

ONICON offers installation hardware kits for commonly used pipe materials. The kits are

specifically designed for ONICON flow meters, and their use is strongly recommended.

The installation instructions contained in this manual assume that the pipe material is

welded steel. Contact ONICON for assistance, if necessary, if the installation involves a

different pipe material.

ONICON offers different types of kits based on the maximum operating pressure and

the maximum fluid temperature. This information is detailed in section 1.4 of this manual.

Contact ONICON for assistance before installing the kit if it does not meet the pressure or

temperature requirements of your application.

IMPORTANT NOTICE

This manual includes detailed installation instructions for welded steel pipe Contact ONICON if

installation hardware instructions are needed for other pipe materials.

i

FLOW

Output signal(s)

to control system

ONICON

Display or

BTU Meter

(Optional)

FLOW DIRECTION