3.5 ELECTRICAL INSTALLATION

Make all connections to the attached 10ft cable.

The most common causes of electronic failures are miswired connections during installation.

When adding additional cable, record and carefully document any substitution of wire colors.

Additional cable may be purchased from ONICON that will allow you to maintain the existing

color coding.

All electrical connections to the F-5200 must be made through the 10ft cable provided with the

meter. This cable is not designed to be removed in the field, and any attempt to do so will

compromise the weather tight integrity of the enclosure.

The cable provided contains 22 AWG color-coded wires for signal and power.

CAUTION

Do not attempt to remove the existing cable or to remove the factory installed connection fitting.

Doing so will compromise the weather tight integrity of the enclosure and may void the warranty.

CAUTION

Only qualified personnel should attempt to make electrical connections to the F-5200. Failure

to properly connect the F-5200 power or signal connections may result in damage to the F-5200

and/or to associated peripheral equipment.

!

!

Wire

Color

Description

Red

+24±4 VDC @ 100 mA

Black

(-) Isolated supply common

Analog Output (Active)

Blue

(+) Isolated analog output

Brown

(-) Analog output common

*Analog Output (Loop Powered)

Blue

(+) Isolated analog output

Yellow

(+) VDC (12 - 24 VDC) External

loop supply voltage

Scaled Output

White

Scaled output, isolated dry

contact, 50 VDC @100 mA

maximum

Orange

*Switch S1 to the loop powered position prior to
applying an external voltage to the yellow wire.

3.5.1 Signal and Power Wiring Connections

½" FNPT

conduit connection

FLOW

Customer provided

conduit and adapters

Output signal(s)

to control

system

ONICON

Display or

BTU Meter

(Optional)

Allow enough slack

in the flexible conduit

to permit the meter

to be removed

from the valve.

Minimum Hole Size = 1"

Must be centered

FLOW DIRECTION