SECTION 4.0: START-UP & COMMISSIONING FOR ONICON

INSERTION THERMAL MASS FLOW METERS

4.1 HELPFUL HINTS FOR START-UP & COMMISSIONING

A step-by-step procedure and companion worksheet are located on the next two pages. Please

read all installation instructions carefully before proceeding with start-up and commissioning.

Please read these helpful hints before proceeding with the start-up and commissioning procedure

on the next page.

1.

ONICON flow meters are individually calibrated for a particular application. Be sure to

verify the pipe size and location.

2.

When measuring analog output signals, remember that current (mA) must be measured

in series, while voltage is measured in parallel. If the 4-20 mA signal is already connected

to a control system, you must break the connection and measure the signal in series.

3.

Do not attempt to rotate the electronics enclosure on the stem.

4.

Do not connect power to the analog output without first confirming that it is configured for

loop powered operation. See section 3.5.2.