11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321

Page 19

SECTION 2.0: MODBUS MEMORY MAP

ONICON Btu meters equipped with MODBUS serial communications provide energy and volume rate
data, and totalized energy and volume data in a variety of engineering units. You select the engineering
units you wish to use by mapping to the appropriate registers.

Also supplied with your System-10 is a document titled “Recommended MODBUS Configuration
Data”. This document is different for each Btu meter. It provides a suggested list of registers to use. The
recommendations are based on the calibration of the flow meter and the programming of units and
multipliers displayed on the System-10.

2.1 MODBUS REGISTER FORMAT AND NETWORKING INFORMATION

1.

All registers are 16 bit MODBUS Holding Registers.

2.

MODBUS Holding Registers are used in 4 different ways.

A.

As an Analog Value: In some cases these values are scaled

by multiplying the register contents by a fixed multiplier.

B.

As a status indicator where the register value can only

be “1” or “2”.

C.

As a mode indicator where the value indicates current operating mode

such as “1” = single, “2” = dual, or “3” = bi-directional.

D.

As a control register where the host can write a value to reset total(s).

3.

Registers 40001 through 40068 are unsigned integer registers (0 to 65,535) except for 40024

and 40025. These are 16 bit signed integer values (-32,768 to +32,767). Registers 41003

through 41081 are 32 bit single precision floating point values. 41001, 41002 and 41065

through 41069 are unsigned integer registers.

4.

System-10 MODBUS register addresses are formatted as follows:

Example: address 4

0001

4 = Holding register

0001 = Address that corresponds to memory location 0000

5.

MODBUS function codes supported:

CODE

DESCRIPTION

03

Read Holding Registers

06

Preset Single Registers

16

Preset Multiple Registers

17

Report Slave ID

i

IMPORTANT NOTE

ONICON provides data in integer and floating point format. We recommend the use of floating

point registers to transmit data to the network. The use of floating point data eliminates the need

for scaling and additional mathematical operations to totalize energy and flow.