ONICON System-10 MODBUS User Manual

Page 5

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321

Page 5

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation procedures and basic operating and servicing

instructions for the ONICON System-10 MODBUS RTU serial interface.

1.2 TYPICAL SYSTEM-10 BTU METER

ONICON’S System-10 is a true heat (Btu) computer, which accepts data from several sensors,

performs a series of computations with that data, and displays and/or transmits the results as an

indication of the amount of heat (Btu’s) being transferred per unit time or as a totalized amount.

1.3 SPECIFICATIONS

MODBUS RTU NETWORK INTERFACE

RS485

Transceiver:

2-wire, half-duplex

Data format:

8 bit with 1 stop bit

Parity: None

MAC address (device address) range: 1 - 247 (Default: 017)

Baud rate:

1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200 (Default: 9600)

Termination: 120 ohms or none (Default: none)

Biasing:

None

Flow control: None

TCP/IP

Transceiver:

10Base T, 10Mbps, Rj45 connection

Data format:

8 bit with 1 stop bit

Parity: None

MAC address (device address) range: 1 - 247 (Default: 017)

Default IP address:

192.168.1.24 (Port 502)

Flow control: None

Heat Exchanger

SCROLL RESET PROGRAM

BTU X 10,000

ONICON insertion

flow meter (purchased

separatelly)

24 VAC input
MODBUS RTU

Communications to

Network

Supply Temp

Sensor

Return Temp

Sensor

Supply

Return

SYSTEM-10

BTU METER