ONICON System-10 MODBUS User Manual

Page 6

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321

Page 6

CAUTION

Only qualified service personnel should make connections between the System-10 BTU Meter

and the user’s external equipment. ONICON assumes no responsibility for damage caused to

the external equipment as a result of an improper installation.

!

Terminal

T1

Do not connect
shields to this
terminal.

CAUTION

Incoming and outgoing RS485 cable shield wires should be connected together, but must not be

connected to the Btu meter.

!

1.4 NETWORK SIGNAL CONNECTIONS

1.4.1 RS485

MODBUS RS485, 2-wire (half-duplex) serial output connections are connected to terminal

T1 as shown. Do not exceed 4.4 in-lb (0.5 Nm) of torque when tightening.