REPORTED PROBLEM

POSSIBLE SOLUTIONS

Network communications are disrupted when the
device is connected (cont.)

• Shield drain connections should be daisy

chained in the same manner as the signal

cables for RS485. The shield drain wire

should be left unterminated at the end of

the cable and connected to earth only at the

network master controller. Shield wires must

not be connected to the RS485 connector on

the System-10.

There are time out errors when polling the
device.

• What registers are you polling for? Polling for

invalid registers will slow the response time.

The range of valid integer registers is 40001

– 40068. The range of valid floating point

registers is 41003 – 41081.

• Resetting totals requires the network

controller to write a 1 to a register in our

device. This takes longer to accomplish than

simply reading registers. This can lead to time

out issues. When dealing with time out errors,

temporarily extend the allowable delay to see

if the problem will go away.