ONICON System-10 MODBUS User Manual

Page 23

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321

Page 23

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ/

WRITE

COMMENT

41059

Mass Total –Lbs

Floating point register (1 of 2)

Read Only

Mass units are only

available when using

F-2000 Vortex meter

41060

Mass Total –Lbs

Floating point register (2 of 2)

Read Only

41061

Mass Total –kg

Floating point register (1 of 2)

Read Only

41062

Mass Total –kg

Floating point register (2 of 2)

Read Only

41063

Auxiliary Input Total (Di3)

Floating point register (1 of 2)

Read Only

41064

Auxiliary Input Total

Floating point register (2 of 2)

Read Only

41065

Zero Mode 1 Energy Total

0 – 1

0 – 1

Not

applicable

Read/Write

Write a value of 1 to

registers to reset totals.

Re-write a value of zero

to the register once the

totals reset.

41066

Zero Mode 1 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

41067

Zero Mode 2 Energy Total

0 – 1

0 – 1

Not

applicable

Read/Write

41068

Zero Mode 2 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

41069

Zero Auxiliary Input Total (Di3)

0 – 1

0 – 1

Not

applicable

Read/Write