ONICON System-10 MODBUS User Manual

Page 21

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321

Page 21

REGISTER

ADDRESS

DESCRIPTION

REG-

ISTER

TYPE

DATA

RANGE

OVER

RANGE

READ/

WRITE

COMMENT

41001

Meter Operating Mode
Indicator

Integer

1 – 3

Not

applicable

Read Only

1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode

41002

Mode Status Indicator

Integer

1 – 2

Not

applicable

Read Only

1 - indicates heating mode

or forward direction

2 - indicates cooling mode

or reverse direction

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ/

WRITE

COMMENT

41003

Energy Rate – Btu/Hr

Floating point register (1 of 2)

Read Only

41004

Energy Rate – Btu/Hr

Floating point register (2 of 2)

Read Only

41005

Energy Rate – kW

Floating point register (1 of 2)

Read Only

41006

Energy Rate – kW

Floating point register (2 of 2)

Read Only

41007

Energy Rate – Tons

Floating point register (1 of 2)

Read Only

41008

Energy Rate – Tons

Floating point register (2 of 2)

Read Only

41009

Volume Rate – GPM

Floating point register (1 of 2)

Read Only

41010

Volume Rate – GPM

Floating point register (2 of 2)

Read Only

41011

Volume Rate – GPH

Floating point register (1 of 2)

Read Only

41012

Volume Rate – GPH

Floating point register (2 of 2)

Read Only

41013

Volume Rate – MGD

Floating point register (1 of 2)

Read Only

41014

Volume Rate – MGD

Floating point register (2 of 2)

Read Only

41015

Volume Rate – L/S

Floating point register (1 of 2)

Read Only

41016

Volume Rate – L/S

Floating point register (2 of 2)

Read Only

41017

Volume Rate – L/M

Floating point register (1 of 2)

Read Only

41018

Volume Rate – L/M

Floating point register (2 of 2)

Read Only

41019

Volume Rate – L/H

Floating point register (1 of 2)

Read Only

41020

Volume Rate – L/H

Floating point register (2 of 2)

Read Only

41021

Volume Rate – M³/Hr

Floating point register (1 of 2)

Read Only

41022

Volume Rate – M³/Hr

Floating point register (2 of 2)

Read Only

41071

Volume Rate - Ft

3

/S

Floating point register (1 of 2)

Read Only

41072

Volume Rate - Ft

3

/S

Floating point register (2 of 2)

Read Only

41073

Volume Rate - Ft

3

/M

Floating point register (1 of 2)

Read Only

41074

Volume Rate - Ft

3

/M

Floating point register (2 of 2)

Read Only

41023

Mass Rate – Lb/Hr

Floating point register (1 of 2)

Read Only

Mass units are only

available when using

an F-2000 Series

Vortex meter

41024

Mass Rate – Lb/Hr

Floating point register (2 of 2)

Read Only

41025

Mass Rate – Kg/Hr

Floating point register (1 of 2)

Read Only

41026

Mass Rate – Kg/Hr

Floating point register (2 of 2)

Read Only

Advertising
This manual is related to the following products: