Programming - standard objects, Technical guide bacnet, Link interface 10 – Orion System BACnet Link User Manual

Page 10: Cw/hw instance number base

Advertising
background image

Technical Guide

BACnet

®

Link Interface

10

Programming - Standard Objects

VavCavOnBoardRelayBits ::= BIT STRING {

OnBoardRelay1

(0),

OnBoardRelay2

(1),

OnBoardRelay3

(2),

OnBoardRelay4

(3),

OnBoardRelqy5

(4),

}

VavCavExRelayGroup1Bits ::= BIT STRING {

ExpansionBoard1Relay1

(0),

ExpansionBoard1Relay2

(1),

ExpansionBoard1Relay3

(2),

ExpansionBoard1Relay4

(3),

ExpansionBoard2Relay1

(4),

ExpansionBoard2Relay2

(5),

ExpansionBoard2Relay3

(6),

ExpansionBoard2Relay4

(7),

}

VavCavExRelayGroup2Bits ::= BIT STRING {

ExpansionBoard3Relay1

(0),

ExpansionBoard3Relay2

(1),

ExpansionBoard3Relay3

(2),

ExpansionBoard3Relay4

(3),

}

VavCavExRelayGroup3Bits ::= BIT STRING {

ExpansionBoard4Relay1

(0),

ExpansionBoard4Relay2

(1),

ExpansionBoard4Relay3

(2),

ExpansionBoard4Relay4

(3),

}

VavCavAlarmBits ::= BIT STRING {

BadSpaceTempSensor

(0),

FanProvingAlarm

(1),

MechanicalCoolingAlarm

(2),

MechanicalHeatingAlarm

(3),

DirtyFilterDetected

(4),

HighSpaceTempAlarm

(5),

LowSpaceTempAlarm

(6),

}

CW/HW Instance Number Base

Instance Number Base For CW/HW Controller

Parameter

Instance

Number

Base

Represented

By

Object

Limits

Alarm Status

17

Analog Input

CO2 Setpoint

42

Analog Value

0

8000

Cold Water Position

44

Analog Input

Configuration

13

Analog Input

Control Mode

11

Analog Input

Control Status

12

Analog Input

Control Temperature

19

Analog Input

Cooling Setpoint

1

Analog Input

Duct Static Pressure

9

Analog Input

Duct Static Setpoint

38

Analog Value

Economizer Position

14

Analog Input

External Relay Group #1

35

Analog Input

External Relay Group #2

36

Analog Input

HCW Configuration

45

Analog Value

0

31

Heating Setpoint

2

Analog Input

Hot Water Position

43

Analog Input

Minimum Outside Air
Setpoint

39

Analog Value

0.01

3

Occupied Cooling Setpoint

32

Analog Value

0

90

Occupied Heating Setpoint

20

Analog Value

0

90

On Board Relay Group

34

Analog Input

Outdoor Air Humidity

10

Analog Input

Outdoor Air Sensor Offset

31

Analog Value

-10

10

Outdoor Air Temperature

8

Analog Input

Outdoor Air Wetbulb

3

Analog Input

Relief Pressure

18

Analog Input

Relief Pressure Setpoint

40

Analog Value

1

99

Return Air CO2 Level

41

Analog Input

-0.3

0.3

Return Air Sensor Offset

30

Analog Value

-10

10

Return Air Temperature

7

Analog Input

Schedule Force

33

Analog Value

0

2

Space Sensor Offset

28

Analog Value

-10

10

Space Temperature

5

Analog Input

Staging Deadband

23

Analog Value

0

10

Supply Air Cooling Setpoint

25

Analog Value

50

70

Supply Air Heating Setpoint

26

Analog Value

0

300

Supply Air Sensor Offset

29

Analog Value

-10

10

Supply Air Temperature

6

Analog Input

Temperature Demand

4

Analog Input

Unoccupied Cooling Setpoint

21

Analog Value

0

30

Unoccupied Heating Setpoint

22

Analog Value

-30

0

Vfd Blower Fan

15

Analog Input

Vfd Exhaust Fan

16

Analog Input

Warm Up Setpoint

27

Analog Value

50

90

Wetbulb Setpoint

24

Analog Value

0

80

Table 5: Instance Number Base Data For CW/HW