General information, Bacnet, Link interface 3 technical guide – Orion System BACnet Link User Manual

Page 3: Data sharing, Scheduling, Hardware specifications, Table 1: bacnet, Link interface technical data, Figure 1: bacnet, Link board components and dimensions

Advertising
background image

BACnet

®

Link Interface

3

Technical Guide

4.00”

4.50"

0.25”

0.25”

7.00"

7.50"

JP1

R1

ADDR.

2

1

C4

U1

EEPROM

NET-

WORK

LOOP

R4

U6

T

SHLD

R

C10

X2

C9

DRIVER

C12

U7

JP4

TERM.

R15

R1
1

R10

R18

RN2

LED

1

LED

2

LED

3

LED

4

NET

COMM

LOOP

COMM

U9

RN1

C7

U2

C2

C3

R3

YS101928

0.20 Dia.
Mounting Hole
Typ. 4 PL.

Mounting
Backplate

Network (MSTP)
Communications
Wiring Terminal

Local Loop
Communications
Wiring Terminal

Local Loop
Communications
Driver Chip

24 VAC Power
Terminals

Network
Communications
LED

Local Loop
Communications
LED

Power
LED

Network
Driver Chip

EPROM Chip
Pin 1 Indicator

Address Switch

RAM Chip
Pin 1 Indicator

TRANSLATOR BOARD

REV 0

U3

EPROM

C8

Q1

PWR

R20

D2

R17

R16

R13

C14

R14

JP3

WDOG

U10

C11

JP2

RAM

U5

U4

SERIAL #

C1

R5

L1

R6 R7

R12

D1

C16

C17

R19

U11

R21

D3

R23

C19

R22

+24VAC

GND

TB3

C13

R8

R9

U8

DRIVER

T

(-)

SHLD

R

(+)

C6

LOOP

LOCAL

C5

X1

VCC

VBAT

R2

The OE367-22 BACnet

®

Link provides bi-directional translation of

data and information between BACnet

®

devices and Orion VAV/CAV,

CW/HW and MUA II unit controllers.

Up to 16 total, Orion VAV/CAV, CH/HW, MUA II or any combination
of these controllers may be connected to each BACnet

®

Link. Up to 4

BACnet

®

Links can be used on a Orion Controls system allowing for

a maximum of 64 total controllers to be used.

Data Sharing

The BACnet

®

Link interface provides the following data sharing capa-

bilities:

Provides values from points on the Orion side of the
gateway to BACnet

®

devices as if the values were

originating from BACnet

®

objects.

Allows BACnet

®

devices to modify point values on the

Orion controller side of the BACnet

®

Link by using

standard BACnet

®

write services

Scheduling

Ability to allow BACnet

®

devices to send Schedule events

to the Orion controller side of the gateway by using
standard BACnet

®

services

Hardware Specifications

Table 1 below contains the hardware specifications for the BACnet

®

Link interface.

T echnical D ata

B A C net L oop

RS-485, Auto D etect H ost
M atching - 9600, 19200, 38400,
76800 B aud R ates

C ontroller L oop

RS-485, 960 0 B aud

P rotocol (B A Cnet Lo op)

M S/T P L an

P rotocol
(W attM aster L oop)

HSI O pen P rotocol
Token Passing

P ow er Input Voltage

24 V A C

P ow er C ons um ption

10 V A M axim um

O perating T em p

10

°

F to 149

°

F

O perating H um idity

90% R H N on-C ondensing

W eight

8 oz

Table 1: BACnet

®

Link Interface Technical Data

General Information

Figure 1: BACnet

®

Link Board Components and Dimensions

Advertising