Orion System BACnet Link User Manual

Page 9

Advertising
background image

BACnet® Link Interface

Technical Guide

9

VAV/CAV Instance Number Base

VAV/CAV BACnet® Property Identifier

The BACnet

®

Link amends the following property identity to BACnet®’s

property identifier.

BACnetPropertyIdentifier :

WattBacScheduleState ::= ENUMERATED {

NormalOperation

(0),

ForceOccupied

(1),

ForceUnoccupied

(2)

}

VavCavControlMode ::= ENUMERATE {

Unoccupied

(0),

RemoteContactOccupied

(1),

NormalScheduleOccupied

(2),

PushButtonOrZoneOverride

(3),

HolidayModeActive

(4),

UnoccupiedZoneDemand

(5),

RemoteScheduleOverride

(6),

CurrentOutputForceMode

(7),

SATHighOrLowCutOff

(8),

CO2OverrideInProgress

(9),

PurgeModeActive

(10)

}

VavCavControlStatusBits ::= BIT STRING {

AhuControlEconomizer

(0),

NoOutdoorAirTempSensor

(1),

CarbonDioxiodeSensorPresent

(2),

HeatCoolStagingDisabled

(3),

DehumidificationMode

(4),

ModGasIIConnected

(5),

ReheatIIConnected

(6),

}

VavCavConfigurationBits ::= BIT STRING {

CoolingDemand

(0),

HeatingDemand

(1),

CoolingEnabled

(2),

HeatingEnabled

(3),

EconomizerEnabled

(4),

FanInStartUpDelay

(5),

WarmUpModeActive

(6),

ProofOfFlow

(7),

HumidistatContact

(8),

ProofOfFlowConfig

(9),

ConstantVolumeConfig

(10),

HeatWheelConfig

(11),

HumiditySensorConfig

(12),

WetBulbSensorConfig

(13),

ReliefPressureConfig

(14)

}

Instance Number Base For VAV/CAV Controller

Parameter

Instance

Number

Base

Represented

By

Object

Limits

Alarm Status

17

Analog Input

CO2 Setpoint

42

Analog Value

0

8000

Configuration

13

Analog Input

Control Mode

11

Analog Input

Control Status

12

Analog Input

Control Temperature

19

Analog Input

Cooling Setpoint

1

Analog Input

Duct Static Pressure

9

Analog Input

Duct Static Setpoint

38

Analog Value

0.01

3

Economizer Position

14

Analog Input

External Relay Group #1

35

Analog Input

External Relay Group #2

36

Analog Input

External Relay Group #3

37

Analog Input

Heating Setpoint

2

Analog Input

Minimum Outside Air
Setpoint

39

Analog Value

1

99

Occupied Cooling Setpoint

32

Analog Value

0

90

Occupied Heating Setpoint

20

Analog Value

0

90

On Board Relay Group

34

Analog Input

Outdoor Air Humidity

10

Analog Input

Outdoor Air Sensor Offset

31

Analog Value

-10

10

Outdoor Air Temperature

8

Analog Input

Outdoor Air Wetbulb

3

Analog Input

Relief Pressure

18

Analog Input

Relief Pressure Setpoint

40

Analog Value

-0.3

0.3

Return Air CO2 Level

41

Analog Input

Return Air Sensor Offset

30

Analog Value

-10

10

Return Air Temperature

7

Analog Input

Schedule Force

33

Analog Value

0

2

Space Sensor Offset

28

Analog Value

-10

10

Space Temperature

5

Analog Input

Staging Deadband

23

Analog Value

0

10

Supply Air Cooling Setpoint

25

Analog Value

50

70

Supply Air Heating Setpoint

26

Analog Value

0

300

Supply Air Sensor Offset

29

Analog Value

-10

10

Supply Air Temperature

6

Analog Input

Temperature Demand

4

Analog Input

Unoccupied Cooling Setpoint

21

Analog Value

0

30

Unoccupied Heating Setpoint

22

Analog Value

-30

0

VFD Blower Fan

15

Analog Input

VFD Exhaust Fan

16

Analog Input

Warm Up Setpoint

27

Analog Value

50

90

Wetbulb Setpoint

24

Analog Value

0

80

Table 4: Instance Number Base Data For VAV/CAV

Advertising