Programming - standard objects, Bacnet® link interface technical guide 7, General information – Orion System BACnet Link User Manual

Page 7: Parameters, Instance number base, Mua ii instance number base

Advertising
background image

BACnet® Link Interface

Technical Guide

7

Programming - Standard Objects

General Information

The BACnet

®

Link provides additional shadowing Analog Input Ob-

jects and Analog Value Objects for read/write parameters of the MUA
II, VAV/CAV and CW/HW controllers.

Note:

The BACnet

®

Link does not implement any operational

function for the Analog Input Object or the Analog Value
Object but only uses the Current Value property of the
Analog Input/Value Object as a vehicle to convey one
specified parameter of the MUA II, VAV/CAV or CW/
HW controller.

Read Only Parameters are represented by Analog Input Objects and
Setpoint Parameters are represented by Analog Value Objects.

Parameters

Parameters for (1) MUA II controller are represented by 36 Analog
Input/Value Objects.

Parameters for (1) VAV/CAV controller are represented by 52 Analog
Input/Value Objects.

Parameters for (1) CW/HW controller are represented by 54 Analog
Input/Value Objects.

Instance Number Base

Each Analog Input/Value Object has an unique Object Instance Num-
ber Base that can be used to identify which parameter the object repre-
sents. The unique Object Instance Numbers are calculated from for-
mula based on the Instance Number Base which are defined in the tables
that follow.

MUA II Instance Number Base

Instance Number Base For MUA II Controller

Parameter

Instance

Number

Base

Represented

By

Object

Limits

Alarm Status

14

Analog Input

Control Status

12

Analog Input

Cooling Deadband

20

Analog Value

2

20

Current Mode

11

Analog Input

Dew Point Reset Limit

27

Analog Value

40

DP Spt.

Dewpoint Setpoint

22

Analog Value

40

80

Enthalpy Deadband

23

Analog Value

3

20

External Heat Position

15

Analog Input

External Heat Proportion
Band

30

Analog Value

1

30

External Relay Group #1

34

Analog Input

External Relay Group #2

35

Analog Input

External Relay Group #3

36

Analog Input

Heating Deadband

21

Analog Value

2

20

Modulate Gas Valve
Position

17

Analog Input

On Board Relay Group

33

Analog Input

Outdoor Air Cooling
Setpoint

3

Analog Input

Outdoor Air Dew Point

5

Analog Input

Outdoor Air Dew Point
Setpoint

6

Analog Input

Outdoor Air Enthalpy

8

Analog Input

Outdoor Air Enthalpy
Deadband

10

Analog Input

Outdoor Air Enthalpy
Setpoint

9

Analog Input

Outdoor Air Heating
Setpoint

4

Analog Input

Outdoor Air Humidity

7

Analog Input

Outdoor Air Temperature

2

Analog Input

Reheat Value Position

18

Analog Input

Schedule Force

32

Analog Value

0

2

Space Humidity

13

Analog Input

Space Humidity At Max
Supply

28

Analog Value

0

100

Space Humidity At Min
Supply

29

Analog Value

0

100

Space Temperature

16

Analog Input

Space Temperature At
Max Supply

25

Analog Value

40

100

Space Temperature At Min
Supply

26

Analog Value

40

100

Supply Air Reset Limit

24

Analog Value

SA

Spt.

SA Spt.

+ 50

Supply Air Setpoint

31

Analog Value

50

90

Supply Air Setpoint Mirror

1

Analog Input

Supply Air Temperature

19

Analog Input

Table 3: Instance Number Base Data For MUA II

Advertising