Bacnet® link interface technical guide 23 – Orion System BACnet Link User Manual

Page 23

Advertising
background image

BACnet® Link Interface

Technical Guide

23

BACnet

®

Services

Objects cannot be dynamically created or deleted by using BACnet

®

Services with the BACnet

®

Link .

BACnet

®

Segmented Requests

BACnet

®

Link does not support segmented requests.

BACnet

®

Segmented Responses

BACnet

®

Link does not support segmented responses.

List Of All Property Identifiers For Proprietary Objects

Property
Identifier

Property Name

Read Or Write

1024

Alarm_Status

R/O

1025

Control_Status

R/O

1026

Cooling_Deadband

R/W

1027

Cooling_Setpoint

R/O

1028

Control_Temperature

R/O

1029

Dew_Point_Reset_Limit

R/W

1030

Dew_Point_Setpoint

R/W

1031

Duct_Static_Setpoint

R/W

1032

Economizer_Position

R/O

1033

Enthalpy_Deadband

R/W

1034

External_Heat_Proportion_Band

R/W

1035

External_Heat_Position

R/O

1036

Heating_Deadband

R/W

1037

Heating_Setpoint

R/O

1038

Modulate_Gas_Valve_Position

R/O

1039

Occupied_Cooling_Setpoint

R/W

1040

Occupied_Heating_Setpoint

R/W

1041

Outdoor_Air_Cooling_Setpoint

R/O

1042

Outdoor_Air_Heating_Setpoint

R/O

1043

Not Used

-----

1044

Not Used

-----

1045

Outdoor_Air_Dew_Point

R/O

1046

Outdoor_Air_Dew_Point_Setpoint

R/O

1047

Outdoor_Air_Enthalpy

R/O

1048

Outdoor_Air_Enthalpy_Setpoint

R/O

1049

Outdoor_Air_Enthalpy_Deadband

R/O

1050

Outdoor_Air_Humidity

R/O

1051

Outdoor_Air_Sensor_Offset

R/W

1052

Outdoor_Air_Temperature

R/O

1053

Outdoor_Air_Wetbulb

R/O

1054

Reheat_Value_Position

R/O

1055

Relays

R/O

1056

Relief_Pressure

R/O

1057

Return_Air_Temperature

R/O

1058

Return_Air_Sensor_Offset

R/W

1059

Schedule_Force

R/W

Table 17: List Of All Property Identifiers

List Of All Property Identifiers For Proprietary Objects

Property
Identifier

Property Name

Read Or Write

1060

Space_Humidity

R/O

1061

Space_Humidity_At_Max_Supply

R/W

1062

Space_Humidity_At_Min_Supply

R/W

1063

Space_Sensor_Offset

R/W

1064

Space_Temperature

R/O

1065

Space_Temperature_At_Max_Supply

R/W

1066

Space_Temperature_At_Min_Supply

R/W

1067

Staging_Deadband

R/W

1068

Supply_Air_Cooling_Setpoint

R/W

1069

Supply_Air_Heating_Setpoint

R/W

1070

Supply_Air_Reset_Limit

R/W

1071

Supply_Air_Sensor_Offset

R/W

1072

Supply_Air_Setpoint

R/W

1073

Supply_Air_Temerature

R/O

1074

Temperature_Demand

R/O

1075

Unoccupied_Coolting_Setpoint

R/W

1076

Unoccupied_Heating_Setpoint

R/W

1077

Vfd_Blower_Fan

R/O

1078

Vfd_Exhaust_Fan

R/O

1079

Warm_Up_Setpoint

R/W

1080

Wetbulb_Setpoint

R/W

1081

Supply_Air_Setpoint_Mirror

R/O

1082

Enthalpy_Unit

R/O

1083

Fan_Speed_Unit

R/O

1084

Humidity_Unit

R/O

1085

Position_Unit

R/O

1086

Temperature_Unit

R/O

1087

Hot_Water_Position

R/O

1088

Cold_Water_Position

R/O

1089

Hcw_Configuration

R./W

1090

Duct_Static_Pressure

R/O

1091

Min_Outside_Air_Setpoint

R/W

1092

Relief_Pressure_Setpoint

R/W

1093

Return_Air_CO2_Level

R/O

1094

CO2_Setpoint

R/O

BACnet

®

Data Link Layer

BACnet

®

Link supports the following data link layer.

Master-Slave/Token Passing (MS/TP) LAN
Data Link Protocol

Tested with Allertons BACtalk

®

Router 200